FREETIME
® -
HEXAMOTION
®
High Efficiency Recovery Unit
OPERATING AND COMMISSIONING INSTRUCTIONS
MS-CDF-010
Ind F
Maj. 18/05/2017
Créé par : JC
Validé par : AR
Page 41/57
48
Internal battery
error
Error battery intern
A
5s
Intern battery of the CORRIGO is disused
Change the battery quickly in order to not loose programm.
See chapter VII.2
49
Sensor error
supply air temp
Control the
Value on Ext AI1
A
5s
Outside temperature sensor SSG is disused
Outside temperature sensor SSG is wrongly connected (see
chapter V.3.a)
50
Sensor error
extract air temp
Contrôler la
valeur sur Ext AI3
A
5s
Outside temperature sensor SRG is disused
Outside temperature sensor SRG is wrongly connected (see
chapter V.3.a)
55
Sensor error
pressure VAS
Control the value
on Ext UAI1
A
5s
0-10V signal is inverted
Pressure transmittor on fresh air is in short-circuit
56
Sensor error
extract VAR
Control the value
on Ext UAI2
A
5s
0-10V signal is inverted
Pressure transmittor on intake air is short circuited
59
CO2 sensor error
Control the
Value on Ext AI4
A
5s
0-10V signal is inverted
CO2 transmittor is in short-circuit
85
… in manual
mode
Functions are
modified in
manual mode
A
5s
In Manuel Auto menu everything must be in Auto.
86
Time for service
Regular visit
C
5s
See chapter VI.3
87
… in manual
mode
Functions are
modified in
manual mode
C
5s
In Manuel Auto menu everything must be in Auto.
VI.3.
Acknowledge the default « timer service »
These settings require an access to the setting menu. You need the access rights to “service” level. Follow the instructions
below.
Enter the code 2222 with directional arrows then press the OK button. Press the left arrow twice to reach the menus. In case of
mistake press C button twice and start again.
An alarm occurs every 6 months to remind the maintenance visit. Enter YES to reset the counter to zero
VII.
MAINTENANCE
Settings
Reset to zero
Filters counter
filter alarm
Reset to zero of the
Timer : YES
access rights
Enter
Enter password 2222
Of the required autoris. level:
Current level : SERVICE