Raccordement électrique et fonctionnement de l’échangeur rotatif
IV.5.a. Version SEASON
Rotative exchanger is factory wired
Son fonctionnement est automatique grâce à deux thermostats :
It automatically runs with two thermostats:
In winter: if outside intake air is lower to 18°C (adjustable), The rotative exchanger starts to recover maximum calories.
In summer:
COLD RECOVERY : if outside intake air is higher to 24°C (adjustable), The rotative exchanger starts to recover maximum
of calories.
FREE COOLING : if outside temperature is between 24° et 18° (adjustable) The rotative exchanger stops to bring directly
outside fresh air
IV.5.b.
Version FIRST PREMIUM
Rotative exchanger is factory wired
CORRIGO controller drives automatically the bypass thanks to programmation and sensor mounted in standard on
FREETIME units.
In winter: when heat is needed, The rotative exchanger starts to recover maximum of calories. If it is not enough to reach the
temperature setpoint, hot battery starts running.
In summer :
COLD RECOVERY : if outside temperature is higher than inside temperature and cold is needed , The rotative exchanger
starts to recover maximum of calories. If it is not enough to reach the setpoint, cold battery starts running.
FREE COOLING : if outside temperature is lower than inside temperature and cold is needed , The rotative exchanger stops to
bring directly outside fresh air. If it is not enough to reach temperature setpoint cold battery starts running.