FREETIME
® -
HEXAMOTION
®
High Efficiency Recovery Unit
OPERATING AND COMMISSIONING INSTRUCTIONS
MS-CDF-010
Ind F
Maj. 18/05/2017
Créé par : JC
Validé par : AR
Page 35/57
V.5.a. Menu configuration en accès service
V.6. Modification of the services parameters (password 2222)
V.6.a. Regulation mode of the unit
[(1) chapter V.5.a]
Access : Configuration / Regulation function.
Regulation type is set by default in the CORRIGO controller in outside compensation exhaust. You can also select return
control mode.
(ATTENTION, if you want to regulate following a room temperature, select the regulation mode« Ctrl extract » Any
other mode will lead to the failure of the unit)
V.6.b. Overventilation parameters
[(2) chapter V.5.a]
Access : Configuration / Night cooling
Night cooling speed is set in standard in 85%. You can modify it. You can also change the temperature of Night Cooling
activation (outside temperature day…) and deactivate it.
V.6.c. CO2 setpoint for DIVA / QUATTRO option
[(3) Chapter V.5.a]
Access: Configuration / Ctrl CO2/COV
CO2 setpoint is set in standard: LS = 800ppm HS = 1000ppm. Unit will increase its speed proportionally to reach its maximum
speed when CO2 will be at 1000ppm.
Configuration
Regulation Function
Night Cooling
Ctrl CO2/VO
Regulation Function
Mode:
Supply t+comp ext (1)
Night cooling activated : YES (2)
Outdoor temp activation : 22°C (2)
Outdoor T° night
High 18°C (2)
Low 10°C (2)
Room mini Temp: 18°C (2)
Speed : 85%
Ctl CO2/COV activated :
If timer ON
Type : Fans
Speed 1/2 : 800 ppm (3)
Speed 1/1 : 1000 ppm (3)
Diff : 160ppm
1.
Regulation type choice (see chapter V.5.b.1)
2.
Parameters modification Night Cooling (see chapter V.5.b.2)
3.
CO2 set point modification (only in DIVA and QUATTRO) (see chapter V.5.b.3)