Alarm setting
Access: Configuration / alarm configuration
Enter alarm number « 10 » go on the right and enter in priority « C alarm C » « Active »
V.8.a.6.
Activation of the function dehumidification
Input settings
Access : Configuration / Input Output / UI / UI4
Declare UI4 input in « Ambiance Humidity »
Function setting
Access: Configuration / Ctrl Humidity
Choose « Dehumidification »
Setpoint setting
Access: Humidity Regul
Enter the required setpoint
VI. REPAIR
VI.1.
Different types of defaults
A specific scrren apear if you have an alarm (see ED-TOUCH manual). Celui -ci sera de classe A, ou C (voir détail ci-dessous)
Type of default:
C : Default do not stop the ventilation system and automatically disappears when a solution is found.
To solve a default press the alarm button (red), « delete » then « enter » the default with directional arrows and press OK
button Attention : do not « block »
Description
Cause
CORRIGO screen do not light up
- Unit is not powered correctly (LED P/B of CORRIGO switched off)
- To light up the screen, press a button (backlit).
- Command fuse is disused
Fans do not start
- Clocks are on 0
- No external start order
- External stop
- Active alarm
Remote control do not run
or gives wrong values
Remote control further than 100m
Repetitor is not connected correctly
VI.2.
List of alarms
n°
View
Description
Type
Tempo
Cause
1
Malfunction
supply air fan
(UDI2 must be
closed « Fer »if
fan runs)
Or
UAI2 must be
higher than 30Pa if
fan runs )
A
30s (120s
for
LOBBY)
1.
Pressure switch is wrongly connected (pressure
switch must be set in 30Pa).
2.
Pressure on the transmittor is lower to 30Pa.
(LOBBY
®
) (contact us)
3.
Motor is disused
4.
Thermic protection motor is activated
5.
Contrôler le raccordement des tubes crystal (chapitre
IV.8 et IV.9
6.
Présence d’eau dans le tube crystal
7.
0-10V motor is inverted