FREETIME
® -
HEXAMOTION
®
High Efficiency Recovery Unit
OPERATING AND COMMISSIONING INSTRUCTIONS
MS-CDF-010
Ind F
Maj. 18/05/2017
Créé par : JC
Validé par : AR
Page 54/57
VII.8.
Table MODBUS et BACNET
INPUT REGISTER
Fonction
Description
Exo
type
Modbus
Adresse
Bacnet
Adresse
Défaut
value
Unit XXXXX
Modbus :
0= stop
1= start
2= start Slow speed
3= start maxi speed
4= start normal speed
5= In operation
8= CO2 functionning
9= Night cooling
11= stopped
BACNET :
1= stop
2= start
3= start Slow speed
4= start speed maxi
5= start normal speed
6= In operation
9= CO2 functionning
10= Night cooling
12= stopped
X
3
MSV, 40003
Outdoor Temperature
R
1
AV, 40001
Operating time of the supply fan
R
4
AV, 40004
Operating time of the extract fan
R
5
AV, 40005
Supply air Temperature
R
7
AV, 40007
Extract Temperature
R
9
AV, 40009
SAF pressure
LOBBY EC
R
13
AV, 40013
EAF pressure
LOBBY EC
R
14
AV, 40014
Supply constant air flow
MAC2
®
/QUATTRO
®
R
15
AV,40015
Extract constant air flow
MAC2
®
/QUATTRO
®
R
16
AV,40016
CO2
DIVA
®
QUATTRO
R
17
AV,40017
Humidity
R
23
AV,40023
Analog output
0-10V Heating (water only)
R
54
Analog output
0-10V Exchanger
R
55
Analog output
0-10V Cooling
R
56
Analog output
0-10V SAF
R
57
Analog output
0-10V EAF
R
58