FREETIME
® -
HEXAMOTION
®
High Efficiency Recovery Unit
OPERATING AND COMMISSIONING INSTRUCTIONS
MS-CDF-010
Ind F
Maj. 18/05/2017
Créé par : JC
Validé par : AR
Page 55/57
HOLDING REGISTER
Fonction
Description
Exo
type
Modbus
Adresse
Bacnet
Adresse
Défaut
value
Supply setpoint
Set in constant supply
R
1
AV, 30001
18
Supply setpoint
Set in constant supply comp ext for T°C out –20°C
R
10
25
Supply setpoint
Set in constant supply comp ext for T°C out de –15°C
R
11
24
Supply setpoint
Set in constant supply comp ext for T°C out de –10°C
R
12
23
Supply setpoint
Set in constant supply comp ext for T°C out de –5°C
R
13
23
Supply setpoint
Set in constant supply comp ext for T°C out de –0°C
R
14
22
Supply setpoint
Set in constant supply comp ext for T°C out de +5°C
R
15
20
Supply setpoint
Set in constant supply comp ext for T°C out de +10°C
R
16
18
Supply setpoint
Set in constant supply comp ext for T°C out de +15°C
R
17
18
Return setpoint
Set in return control
R
18
AV, 30018
21
speed supply HS setpoint
In % for ECO and DIVA
R
424
70
speed supply LS setpoint
In % for ECO and DIVA
R
425
50
speed return HS setpoint
In % for ECO and DIVA
R
426
70
speed return LS setpoint
In % for ECO and DIVA
R
427
50
pressure soufflage setpoint
In Pa for LOBBY
R
25
AV, 30025
150
pressure reprise setpoint
In Pa for LOBBY
R
27
AV, 30027
150
Airflow supply HS setpoint
In m3/h for MAC2
®
and QUATTRO
®
R
28
AV,30028
xxx
Airflow supply LS setpoint
In m3/h for MAC2
®
and QUATTRO
®
R
29
AV,30029
xxx
Airflow return HS setpoint
In m3/h for MAC2
®
and QUATTRO
®
R
30
AV,30030
xxx
Airflow return LS setpoint
In m3/h for MAC2
®
and QUATTRO
®
R
31
AV,30031
xxx
Forçed
Functionning mode of the unit
MODBUS
0= Manual stop
1= Manual slow speed
2= Vitesse normale manuelle
3= Auto
BACNET
1= manual stop
2= Manual slow speed
3= Normal manual speed
4= Auto
X
368
MSV,30368 xx:xx