![Burkert 8756 BATCH Operating Instructions Manual Download Page 28](http://html1.mh-extra.com/html/burkert-0/8756-batch/8756-batch_operating-instructions-manual_2832389028.webp)
Type 8756 BATCH
Commissioning
28
7
COMMISSIONING
7.1
Safety instructions
WARNING!
Risk of injury that is due to the operating pressure.
▶
Make sure that the product operating-pressure is not higher than the operating pressure value on the
product data-sheet. Find the data sheet on our homepage:
WARNING!
Risk of injury from improper operation.
Improper operation can lead to injuries and damage to the product and its environment.
▶
Before commissioning, make sure that the operating personnel are familiar with, and fully understand the
content of the Operating Instructions.
▶
Observe the safety information and the intended use.
▶
Only properly trained personnel may commission the installation and the product.
▶
Only properly trained personnel may change parameters with the help of the Bürkert Communicator
software.
7.2
Commissioning procedure (MFC with on/off valve)
The operation of the product is tested at the factory with fluid. Residual fluid can remain in the flu-
idic parts of the product.
No zero adjustment is needed.
Pressurise the pipes with operating fluid.
Make sure that the on/off valve is completely open.
Flush the pipes with operating fluid.
Vent the pipes completely.
Connect the product to the Bürkert Communicator software. Refer to chapter
the Bürkert Communicator software [
Flush bubbles from the pipes as described in chapter:
Flush bubbles from the pipe (MFC with on/off
Wire the product again as described in chapter
.
Energise the product.
If product-specific data is stored on the inserted memory card, then the product adopts the data. To
get a list of the stored data at product delivery, refer to the Help for the Initiation file that can be
downloaded from
.
If the inserted memory card is empty, then the product loads its own data on the memory card.
Possible problems related to the memory card are given in chapter: