Type 8756 BATCH
Setting and operation
39
Go to
General settings
>
Parameters
>
büS
>
Advanced
>
Bus mode
Choose the operating mode of the digital communication.
Restart the product.
The operating mode of the fieldbus is changed.
If the operating mode of the fieldbus is büS, then the
CANopen status
is set to
Operational
and the
PDOs are sent to büS.
If the operating mode of the fieldbus is CANopen, then the
CANopen status
is set to
Pre-Op
until the
CANopen network master switches the product to
Operational
.
8.7
Transmission speeds of cyclic data
The product transmits cyclic data at the following transmission speeds:
▪
once every 500 ms by default if the value of a PDO is constant. The transmission speed of each PDO
can be changed. Refer to
Change the transmission speed of a single PDO [
▪
once every 100 ms by default if the value of a PDO changes. If the bus load does not exceed 50%, then
the transmission speed can be increased temporarily to 10 ms. Refer to
transmission speed of all PDOs [
8.7.1
Change the transmission speed of a single PDO
In the Bürkert Communicator software, select the product.
The product status indicator flashes.
Go to
General settings
>
Parameters
>
PDO Configuration
Set the value of the
Inhibit time
for each PDO.
The transmission speed of the PDO is changed.
8.7.2
Temporarily increase the transmission speed of all PDOs
If the transmission speed is increased simultaneously on several products in the network, then make sure
that the bus load does not exceed 50%.
Energise the bus network.
Connect the product to the Bürkert Communicator software. Refer to
Connect the product to the Bürk-
In the Bürkert Communicator software, move the PC mouse over the büS-stick symbol in the list of
devices:
▪
If the bus load is higher than 45%, then do not increase the transmission speed.
▪
If the bus load is less than or equal to 45%, then the transmission speed can be increased. Do the fol-
lowing procedure:
In the Bürkert Communicator software, select the product.
The product status indicator flashes.
Go to
General settings
>
Diagnostics
>
Inhibit time
.
To increase the transmission speed, click
Set diagnostic mode
. The function
Inhibit time
switches to
Set to default values
.
The transmission speed of all the PDOs is increased.