Type 8756 BATCH
Setting and operation
34
Bit
Event
Product status indicator
3
Memory error
red
A product memory is defective.
A maintenance operation is needed. Contact the manufacturer.
4
Sensor error
red
The product sensor is defective.
A maintenance operation is needed. Contact the manufacturer.
5
Flow-rate sensor: calibration curve temporarily repaired
blue
The calibration curve is defective and has been repaired.
A maintenance operation is needed. Contact the manufacturer.
6
Fluid temperature outside specification
yellow
The fluid temperature is outside the specification.
Operate the product within the specifications.
7
Flow-rate sensor: switch on / initialize
yellow
The product sensor is being initialized.
Wait until the sensor is initialized.
If the initialization fails (this results in an error bit 4), restart the product.
If it still fails, contact the manufacturer.
8
Bubbles in the product
yellow
The product has detected bubbles in the liquid.
Flush bubbles from the pipe. refer to chapter 10.5.3.
9
Empty pipe detected
yellow
The product has detected that the pipe is empty.
Fill the pipe with fluid. Make sure that the fluid flows.
10
Zero-point adjustment in progress
orange
A procedure to adjust the zero-point is performed on the product.
Wait until the procedure is finished.
if zero-point adjustment failed, try it again with stabel conditions.
11
Override actuator
orange
The closed-control loop is deactivated. A direct signal is sent to the actuator.
Deactivate the direct control of the actuator.
Actuator
>
Actuator override
>
Automatic
12
Reserved
13
Leackage detected
yellow
The product has detected a leackage.
Replace the on/off valve. Refer to
Replace the on/off valve Type 6013 [
14...19
Reserved