Dual EOL mode
Each of the required pins will need to be wired as shown below.
You will need 1 x 3K3 and 1 x 10K resistors for each pin with DEOL interconnection
monitoring. These are available from the BT Redcare installer shop
To pin input
Normally open
contacts
E0L resistor 1
EOL resistor 2
10K
3K3
12V or 24V supply input
To alarm input (pin)
Normally open
contacts
EOL resistor
10K
12V or 24V supply input
Interconnection monitoring
If the signalling unit is remote from the alarm panel, it’s possible to wire the pin inputs
to be able to detect open or short circuits on the interconnection wiring between the
panel and the unit.
To enable interconnection monitoring, you need to program the unit via the
configuration menu, app or web portal.
End of Line
Single EOL mode
Each of the required pins will need to be wired as shown below.
Resistor
Item Code Label
Colour Code
3K3
089446
Red Dot in packet
10K
089447
Blue Dot in packet
brown, black, black, red, brown
10K
Ω
1%
3.3K
Ω
1%
orange, orange, black, brown, brown