Commissioning
B 3
ekrPro Com
60
web guide controller
EDV No.:
MD.191.01.05/1.6.x Chapter:
B 3
with analog sensors
Date:
23.11.2007
Page:
5/73
B 3.3.2 Terminator activation
The terminator must be activated on each of the physical first and
last CAN bus participants. The possible settings are described
below.
B 3.3.2.1
ekrPro Com
60
In the ekrPro Com
60
, the activation is carried out using switch S3 on
the processor circuit board. Set the switch to "ON“.
Procedure:
1. Switch-off the power to the controller.
2. Open controller’s front cover.
3. Activate terminator S3 (switch position ON)
4. Close the controller’s front cover.
5. Restore the power.
B 3.3.2.2
ekrPro Key
60
(if fitted)
In the ekrPro Key
60
activation
is carried out via switch
S3
.
Remove plug on the
back side.
Set the switch to "ON“.
Switch
S3
Terminator
S3