186CNV / 284ANV: Service Manual
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
6
Non-Communicating Control
The non-communicating control connections are shown in Fig. 5.
Specific connections depend on system configuration. Note that O and
W are driven during Defrost for heat pump models.
A200240
Fig. 5 – Non-Communicating Control Connection
In non-communicating mode, the Performance Mode and Defrost
Interval are set using DIP switches. Switch assignments are shown in
. Switch settings are shown in the tables that follow.
A200241
Fig. 6 – Non-Communicating DIP Switch Assignment
Table 1 – DIP Swtich Settings
IMPORTANT:
The R (Rc) signal on the PCM comes from the
transformer in the equipment. The phase of this transformer connection
is not controlled relative to the phase of the transformer in the indoor
equipment (Rh). Wiring requirements in this manual do not connect Rc
and Rh together. For any non-standard wiring, care should be taken to
make sure that Rc and Rh are not connected together. Doing so may
result in destroying one or both of the transformers in this and the
internal equipment.
PCM Indicators and Matrix Display
The PCM contains three indicator lights (LEDs) and a dot matrix
display. Indicator and display location is shown in
. The
indicators are described briefly below. Indicator operation and
interpretation is described in the Control Features section.
Status Light
The status light is a single color amber LED that indicates equipment
operating status and diagnostic conditions.
Comm Light
The Comm light is a single color green LED that indicates the
communication state and system control state of the equipment.
VFD Comm Light
The VFD Comm Light is a bi-color red / green LED that indicates the
communication with the VFD.
Matrix Display
The matrix display is a 5x7 dot matrix for displaying messages and
diagnostic information.
Switch 1
Switch 2
Defrost Interval
Up
Up
Auto
Up
Down
30 minutes
Down
Up
60 minutes
Down
Down
90 minutes
Switch 3
Performance Mode
Up
Efficiency
Down
Comfort
O
W
Y2
Y1
C
LLS
UT
IL
NON-COMMUNICATING
CONTROL CONNECTIONS
NOTE: O should be acve in Cooling
Performance Mode
Defrost Interval
4
3
2
1
ON
Not Used