Bryant Evolution Extreme 186CNV Service Manual Download Page 17

186CNV / 284ANV: Service Manual

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

17

Code 32-59 Low Pressure Lockout

This fault is triggered when the suction pressure is too low to safely start
the  compressor.  If  refrigerant  saturated  pressure  is  low  enough  the
system will be inoperable until pressures increase to acceptable range.
System  will  be  inoperable  while  this  fault  is  active.  The  most  likely
cause of this fault is a leak in the refrigeration system.

Code 33-15 Compressor Low Discharge Shutdown
Code 33-55 Compressor Low Discharge Lockout

Code 33-15 will become active if compressor is running and discharge
pressure is below the lower safe operating boundary for a period of time.
Discharge low pressure boundary only applies to the 5 ton model. Active
envelope  management  will  attempt  to  modify  system  operation  to
correct this condition before fault is set, but once time limit beyond the
limit is exceeded the system will shutdown. 6 occurrences of code 33-15
within 2 hours will result in code 33-55 and 2 hour lockout.
Low  discharge  pressure  can  be  caused  by  malfunctioning  reversing
valve,  low  charge,  missing  or  stuck  TXV/EXV,  or  compressor  not
operating properly.

Code 34-11 Compressor High Temp Limiting
Code 34-58 Compressor High Temp Lockout

Code  34-11  will  be  set  when  discharge  temperature  exceeds  230F
measured near the compressor. Low charge or very high superheat are
contributors  to  this  fault  condition.  For  each  occurrence  of  34-11,  the
next startup will  operate at  a  25%  reduction in capacity. Each hour of
operation  without  additional  faults  will  allow  system  to  increase
available  capacity  by  25%.  Once  the  system  is  running  at  minimum
capacity and discharge temperature exceeds 230F, code 34-58 will occur
and shut down system for 2 hours.

Code 35-11 Compressor High Compress Limiting
Code 35-58 Compressor High Compression Lockout

Code 35-11 occurs when the high compression boundary is crossed and
AEM cannot adjust system operation to reduce compression ratio. For
each  occurrence  of  35-11,  the  next  startup  will  operate  at  a  25%
reduction in capacity. Each hour of operation without additional faults
will  allow  system  to  increase  available  capacity  by  25%.  Once  the
system  is  running  at  minimum  capacity  and  the  high  compression
boundary is crossed, code 35-58 will occur and shut down system for 2
hours.  High  compression  ratio  can  be  the  result  of  overcharge  or  coil
blockage/loss of airflow across heat exchanger.

Code 36-15 Compressor Low Compress Shutdown
Code 36-55 Compressor Low Compression Lockout

Code 36-15 occurs when the low compression boundary is crossed and
AEM  cannot  adjust  system  operation  to  increase  compression  ratio.
Before  this  fault  is  set,  AEM  will  automatically  reduce  outdoor  fan
speed (cooling only) to increase CR, then increase compressor speed. 4
occurrences of code 36-15 within 2 hours will result in code 36-55 and 2
hour lockout. Low compression ratio can be a result of compressor not
increasing pressure adequately or low system charge.

Code 38-13 VFD Compressor Fault - Start Fail
Code 38-53 VFD Compressor Lockout - Start Fail

Code  38-13  originates  in  VFD  after  additional  compressor  starting
failures. While this code is active the unit opens PEV in an attempt to
equalize  pressure  across  compressor  and  continue  start  retries. After  3
consecutive  code  38-13,  malfunction  38-53  will  be  set  with  a  2  hour
lockout

Check compressor wiring for secure connections, wire damage, and wire

order.  This  code  indicates  that  the  VFD  is  not  able  to  rotate  the
compressor  rotor  enough  to  complete  starting  process,  indicating
compressor  damage  or  high  pressure  differential.  If  malfunctions

continue  to  be  generated  and  technician  confirms  pressure  differential
across compressor is <40psi, replace compressor.

Code 38-18 High Diff Pressure Start Disable

Attempting  to  start  the  compressor  against  a  high  pressure  differential
may  result  in  start  failures  with  an  otherwise  healthy  compressor. The
PEV  is  included  to  ensure  compressor  will  never  start  against  a  high
pressure  differential. This  fault  will  become  active  if  a  demand  exists
and  the  PEV  is  not  successful  in  lowering  pressure  differential  below
100psi. The  fault  will  clear  and  unit  will  start  normally  once  pressure
differential is below 100psi and demand is still present.
The most likely cause of this fault is a non-functioning PEV. Possibly the
PEV suffered a mechanical failure, or the coil is not mounted to PEV.
Verify  PEV  coil  is  attached  to  PEV  valve  body.  If  coil  is  attached  to
body, replace PEV harness and coil first, and PEV body if problem is not
fixed.

Code 38-31 VFD Compressor Fault - Estimator
Code 38-71 VFD Compressor Lockout - Estimator

The VFD  Estimator  is  used  in  the  compressor  starting  process. While
this  fault  is  active  the  PEV  will  open  and  compressor  will  continue
attempts at restarting. Three continuous code 38-31 will result in code
38-71 malfunction and 4 hour lockout. Repeated malfunctions indicate
high starting torque and possible compressor damage. First, ensure the
VFD model and compressor models are correct for unit being serviced as
incorrect  compressor  motor  parameters  will  not  allow  the  VFD  to
complete  the  starting  process  correctly.  If  all  parts  are  correct  for  the
model being serviced, compressor damage exists and should be replaced.

Code 38-54 Compressor No Pump Lockout

This diagnostic checks to ensure the compressor is running in the correct
direction and pumping properly. Once the compressor speed is >400rpm,
the compressor has up to 30 seconds to increase the pressure differential
(discharge  pressure  -  suction  pressure)  by  20psi.  If  this  pressure
differential  is  not  met,  code  38-54  sets  by  locking  operation  for  30
minutes.
The most likely cause of this fault is the compressor leads being wired
incorrectly. Check  wire colors against  wiring diagram to ensure UVW
wires are attached to the correct terminals. Less likely but still possible is
compressor motor  shaft  breakage  allowing  compressor  motor  to  rotate
but is disconnected from compression mechanism.
Fan Motor Faults General Info
The fan motor used on these models require 5 wires. 240~373 VDC is
supplied  through  Pin  1  of  3  pin  connector  (VDC)  and  Pin  1  of  4  pin

connector (GND). Pin 2 of 4 pin connector is Vcc signal for IC power
supply  (~15Vdc).  Pin  3  of  4  pin  connector  is  Vsp  signal,  which  is
0-5VDC input speed  control. Pin 4 of 4 pin is FG or feedback signal,

sending rpm information back to VFD. The motor is controlled using a
closed  loop  control  where  variable  speed  is  increased  or  decreased  by
VFD depending on the RPM command from PCM to VFD along with
actual  RPM  information  read  through  FG  pin.  Use 

Table 6

  to  confirm

damaged electronics within fan motor. Note - winding resistance cannot
be  measured  on  fan  motor  due  to  embedded  electronics.  Note  -
resistances  are  approximate,  temperature  may  affect  measurements  so

only declare motor bad if results differ greatly from values in 

Table 3

.

Though  the  fan  motor  has  internal  current  protection,  an  external
replaceable  fuse  is  located  on  VFD  for  short  circuit  protection.  See

wiring diagram for fuse replacement specifications.

Summary of Contents for Evolution Extreme 186CNV

Page 1: ...nt Low Fan Speed 9 Fan Operating Exceptions 9 Cooling Control 9 Heating Control 9 Super Heat Control 9 Defrost Mode 9 Defrost Interval 10 Defrost Process 10 PCM Indicators and Display Operation 10 Sta...

Page 2: ...ves a Seasonal Energy Efficiency Ratio SEER of up to 24 and up to 13 Heating Seasonal Performance Factor HSPF and the AC achieves up to 26 SEER To ensure all of the above technology provides the ultim...

Page 3: ...not controlled relative to the phase of the power provided by the transformer in the indoor equipment Rh Wiring requirements in this manual do not connect Rc and Rh together For any non standard wiri...

Page 4: ...any time specifications and designs without notice and without obligations 4 Fig 2 Compressor Fan Sub System Diagram Fig 3 Wiring Diagram 186CNV 284ANV Model sizes 2 5 tons 208 230 1 FILTER REACTOR S...

Page 5: ...0 rpm to 800 rpm depending on air movement requirements The fan on board VFI will automatically limit fan speed if fan load current reaches operating limits Crankcase Heater Some equipment has a crank...

Page 6: ...sure that Rc and Rh are not connected together Doing so may result in destroying one or both of the transformers in this and the internal equipment PCM Indicators and Matrix Display The PCM contains t...

Page 7: ...he right to change at any time specifications and designs without notice and without obligations 7 A200049 A200044 Fig 7 PCM Control Board Bluetooth Service Port Status LED Yellow CCN Communication LE...

Page 8: ...alve for regulating refrigerant flow during heating operation The EXV H is driven by a 12VDC 2 phase uni polar stepper motor The EXV H has a 475 step range between fully closed and fully open The PCM...

Page 9: ...oor equipment and under charged or over charged systems Sump Heat When the compressor is not running the compressor sump may need to be heated to prevent liquid refrigerant from collecting in the sump...

Page 10: ...e Comm light is On then communication has been received within the last 2 minutes and the equipment is operating in normal communication mode If the Comm light is Off then communication has not been r...

Page 11: ...No code will be displayed if the most recent highest priority diagnostic code occurred more than 240 hours of equipment operating time before entering recall mode No code will be displayed if there ha...

Page 12: ...nd indoor fan for proper operation Low Pressure Protection The equipment monitors suction pressure relative to low pressure limits Low pressure limits are compressor speed and model dependent If the c...

Page 13: ...oil Temperature OCT Thermistor The OCT thermistor provides the coil liquid line temperature to the PCM where it is used primarily for defrost control The OCT thermistor is located on an extension tube...

Page 14: ...dentical Either pressure transducer can connected to either input The software in the PCM detects which transducer is connected to which input and assigns the signals accordingly Signals used by contr...

Page 15: ...s received by PCM If this fault is active inspect PCM to Bluetooth module harness and ensure both ends are fully seated on board header Also inspect and repair any wire damage on harness If no green o...

Page 16: ...This code will be set if fuse 2 is blown or missing on PCM board Fuse 2 only powers the LLS When this fault is active the system will not operate The code will clear once fuse is replaced with new un...

Page 17: ...connections wire damage and wire order This code indicates that the VFD is not able to rotate the compressor rotor enough to complete starting process indicating compressor damage or high pressure dif...

Page 18: ...equired from compressor and VFD The PEV will open 2 5 minutes after compressor shutdown if pressure differential is between 200 300psi or if pressure differential is greater than 50psi and demand is p...

Page 19: ...observed replace sensor If measured resistance is within allowable range replace PCM Code 54 02 ODT Shorted The discharge thermistor is used to protect the compressor and ensure discharge superheat i...

Page 20: ...will operate to a known position as the valve does not have the capability to feedback actual position The PCM software must know the starting point and then count when stepper motor is pulsed At the...

Page 21: ...ill be reduced to 0 If measurement is open replace reactor Otherwise replace VFD Code 81 14 VFD System Fault Unbalanced PFCM Code 81 54 VFD System Lockout Unbalance PFCM Applicable to 4 and 5 ton mode...

Page 22: ...resistance against table Listen to compressor during operating for abnormal noise indicating physical damage VFD may have internal damage causing high current or compressor may be damaged Code 83 57 V...

Page 23: ...with disconnect if malfunction persists replace VFD Code 88 32 VFD Internal Fault IPM Temp Sens The VFD has internal temperature sensors to monitor critical power components and take action if operati...

Page 24: ...ue to operate normally since the only way to correct this fault is to replace VFD Code 88 38 VFD Internal Fault DC Discharge Code 88 78 VFD Lockout Int DC Discharge The unit VFD converts boosts 230VAC...

Page 25: ...55 Compressor Low Discharge Limit 34 11 58 Compressor High Temperature Limit 35 11 58 Compressor High Compression Limit 36 15 55 Compressor Low Compression Limit 38 13 53 Compressor Starting Error 54...

Page 26: ...t Limit 1 Speed Reduction 12 Compressor Current Limit 2 Speed Reduction 15 55 Compressor Current Limit 3 Shutdown 16 56 Compressor Current Limit 4 Shutdown 57 Compressor Underspeed Shutdown 84 11 58 V...

Page 27: ...nd designs without notice and without obligations 27 A200187 Fig 18 2T 3T Control Box A200188 Fig 19 4T 5T Control Box Note 4T VFD similar not exact 5T reactors have additional chokes to meet FCC requ...

Page 28: ...otice and without obligations 28 A200191 Fig 22 2 3T VFD Connections VFD control relay and LED Fan motor connections VFD to PCM comm connection DC DC terminals Fan motor fuse Compressor UVW connection...

Page 29: ...192 Fig 23 4 5T VFD Connections Note 4T uses separate terminals VFD to PCM comm connection Fan motor connections Compressor UVW connections DC DC terminals Reactor connection Filter board input VFD co...

Page 30: ...186CNV 284ANV Service Manual Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 30 A200193 Fig 24 PCM used on all models...

Page 31: ...designs without notice and without obligations 31 A200194 Fig 25 Bluetooth Module used on all models A200195 Fig 26 Fan Motor used on all models A200196 Fig 27 2 3 4T Rector Note 4Tuses 2 reactors A2...

Page 32: ...rer reserves the right to change at any time specifications and designs without notice and without obligations 32 A200199 Fig 30 PCM to Bluetooth Module Comm Cable used on all models A200200 Fig 31 VF...

Page 33: ...186CNV 284ANV Service Manual Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 33 A200201 Fig 32 PCM Wiring Diagram...

Page 34: ...brazing alloy is used on copper to brass copper to steel or copper to copper Flux is required when using silver brazing alloy Do not use low temperature solder 3 Fluxes should be used carefully Avoid...

Page 35: ...flow of refrigerant in system This reversing valve device is easy to troubleshoot and replace The reversing valve solenoid can be checked with power off with an ohmmeter Check for continuity and shor...

Page 36: ...where acid might occur such as burnout Heat pump units must have the drier installed between the compressor and accumulator only Remove after 10 hours of operation Never leave suction line filter drie...

Page 37: ...l eventually fail from lack of lubrication If bleed hole is plugged accumulator must be changed The accumulator has a fusible element located in the bottom end bell See Fig 37 This fusible element wil...

Page 38: ...igerant is leaking at that point A simple and inexpensive method of testing for leaks is to use soap bubbles See Fig 40 Any solution of water and soap may be used Soap solution is applied to all joint...

Page 39: ...ngthen careers and businesses We believe in providing high quality learning experiences both online and in the classroom Access My Learning Center with your HVACpartners credentials at www mlctraining...

Page 40: ...Company Edition Date 06 20 Catalog No SM186CNV 284ANV 01 Replaces NEW 186CNV 284ANV Service Manual Manufacturer reserves the right to change at any time specifications and designs without notice and...

Reviews: