Bryant Evolution Extreme 186CNV Service Manual Download Page 38

186CNV / 284ANV: Service Manual

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

38

Vapor Injection Electronic Exp. Valve (EXV VI)
(5 Ton Models)

The EXV-VI is an electronically controlled needle valve for regulating
refrigerant flow during heating operation.  The EXV-VI is driven by a
12VDC, 2-phase, uni-polar stepper motor.  The EXV-VI has a 475 step

range between fully closed and fully open. The PCM drives the EXV at a
rate  of  77  steps  per  second.    The  PCM  initializes  the  EXV-VI  to  the
closed position when power is applied to the equipment.  This process

takes approximately 7 seconds.
When  operating  at  full  capacity  in  a  cooling  at  high  ambient
temperatures  or  in  heating  at  low  ambient  temperatures  in  efficiency
mode,  the  EXV-VI  is  actively  controlled  to  maintain  discharge  super
heat  to  a  control  target  value.   When  operating  at  a  lower  capacity,  in

comfort  mode,  at  mild  ambient  temperatures,  or  not  running,  the
EXV-VI is closed.
The brazed  plate heat exchanger assembly is mounted  to  the base  pan
using  a  grommet  and  stud  similar  to  the  accumulator  mounting.    The

BPHE assembly also contains a muffler either between the BPHE and
the  compressor  or  between  the  BPHE  and  the  liquid  service  valve.
Additionally, there are rubber dampers attached to the tube between the

BPHE and the compressor.  
If  any  part  of  the  BPHE  needs  to  be  repaired  then  only  a
factory-authorized part shall be used to replace the entire vapor injection
assembly.    It  is  recommended  that  the  coil  be  removed  to  replace  the

BPHE  assembly.    Upon  replacement  the  grommet  and  clip  used  for
mounting  can  be  re-used  and  the  dampers  shall  be  re-attached  to  the
BPHE assembly using a wire tie.  Failure to re-attach the dampers could

result in a premature tube failure."

REFRIGERATION SYSTEM REPAIR

Leak Detection

New  installations  should  be  checked  for  leaks  prior  to  complete

charging.  If a system has lost all or most of its charge, system must be
pressurized  again  to  approximately  150  psi  minimum  and  375  psi
maximum. This can be done by adding refrigerant using normal charging

procedures or by pressurizing system with nitrogen (less expensive than
refrigerant).  Nitrogen  also  leaks  faster  than  refrigerants.    Nitrogen
cannot,  however,  be  detected  by  an  electronic  leak  detector.  (See

Fig. 39

.)

A95422

Fig. 39 – Electronic Leak Detection

Assuming  that  a  system  is  pressurized  with  either  all  refrigerant  or  a
mixture  of  nitrogen  and  refrigerant,  leaks  in  the  system  can  be  found
with  an  electronic  leak  detector  that  is  capable  of  detecting  specific

refrigerants.
If  system  has  been  operating  for  some  time,  first  check  for  a  leak
visually. Since refrigerant carries a small quantity of oil, traces of oil at
any joint or connection is an indication that refrigerant is leaking at that

point. 

A  simple  and  inexpensive  method  of  testing  for  leaks  is  to  use  soap

bubbles.  (See 

Fig. 40

.) Any  solution  of  water  and  soap  may  be  used.

Soap solution is applied to all joints and connections in system. A small

pinhole leak is located by tracing bubbles in soap solution around leak. If

the  leak  is  very  small,  several  minutes  may  pass  before  a  bubble  will

form.  Popular  commercial  leak  detection  solutions  give  better,

longer-lasting bubbles and more accurate results than plain soapy water.

The bubble solution must be removed from the tubing and fittings after

checking for leaks as some solutions may corrode the metal.

A95423

Fig. 40 – Bubble Leak Detection

You may use an electronic leak detector designed for specific refrigerant
to check for leaks (See 

Fig. 39

). This unquestionably is the most efficient

and  easiest  method  for  checking  leaks.  There  are  various  types  of

electronic  leak  detectors.  Check  with  manufacturer  of  equipment  for
suitability.  Generally  speaking,  they  are  portable,  lightweight,  and
consist of a box with several switches and a probe or sniffer. Detector is

turned  on  and  probe  is  passed  around  all  fittings  and  connections  in
system. Leak is detected by either the movement of a pointer on detector
dial, a buzzing sound, or a light.
In all instances when a leak is found, system charge must be recovered

and leak repaired before final charging and operation.  After leak testing
or leak is repaired, replace liquid line filter drier, evacuate system, and
recharge with correct refrigerant quantity.

Coil Removal

Coils  are  easy  to  remove  if  required  for  compressor  removal,  or  to
replace coil.

1. Shut off all power to unit.
2. Recover refrigerant from system through service valves.
3. Break vacuum with nitrogen.
4. Remove top cover. 
5. Remove screws in base pan to coil grille.
6. Remove coil grille from unit.
7. Remove screws on corner post holding coil tube sheet.

8. Use midget tubing cutter to cut liquid and vapor lines at both sides

of coil. Cut in convenient location for easy reassembly with copper

slip couplings.

9. Lift coil vertically from basepan and carefully place aside.
10. Reverse procedure to reinstall coil.
11. Replace  filter  drier,  evacuate  system,  recharge,  and  check  for

normal systems operation.

WARNING

!

PERSONAL INJURY AND UNIT DAMAGE  HAZARD

Failure to follow this warning could result in personal injury or death.
Due to the high pressure of nitrogen, it should never be used without a
pressure regulator on the tank.

BEEP

BEEP

WARNING

!

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.
Before  installing,  modifying,  or  servicing  system,  main  electrical
disconnect switch must be in the OFF position. There may be more than
1 disconnect switch. Lock out and tag switch with a suitable warning

label. 

WARNING

!

FIRE HAZARD

Failure  to  follow  this  warning  could  result  in  personal  injury  or
equipment damage.
Cut tubing to reduce possibility of personal injury and fire.

LEAK

DETECTOR

SOLUTION

Summary of Contents for Evolution Extreme 186CNV

Page 1: ...nt Low Fan Speed 9 Fan Operating Exceptions 9 Cooling Control 9 Heating Control 9 Super Heat Control 9 Defrost Mode 9 Defrost Interval 10 Defrost Process 10 PCM Indicators and Display Operation 10 Sta...

Page 2: ...ves a Seasonal Energy Efficiency Ratio SEER of up to 24 and up to 13 Heating Seasonal Performance Factor HSPF and the AC achieves up to 26 SEER To ensure all of the above technology provides the ultim...

Page 3: ...not controlled relative to the phase of the power provided by the transformer in the indoor equipment Rh Wiring requirements in this manual do not connect Rc and Rh together For any non standard wiri...

Page 4: ...any time specifications and designs without notice and without obligations 4 Fig 2 Compressor Fan Sub System Diagram Fig 3 Wiring Diagram 186CNV 284ANV Model sizes 2 5 tons 208 230 1 FILTER REACTOR S...

Page 5: ...0 rpm to 800 rpm depending on air movement requirements The fan on board VFI will automatically limit fan speed if fan load current reaches operating limits Crankcase Heater Some equipment has a crank...

Page 6: ...sure that Rc and Rh are not connected together Doing so may result in destroying one or both of the transformers in this and the internal equipment PCM Indicators and Matrix Display The PCM contains t...

Page 7: ...he right to change at any time specifications and designs without notice and without obligations 7 A200049 A200044 Fig 7 PCM Control Board Bluetooth Service Port Status LED Yellow CCN Communication LE...

Page 8: ...alve for regulating refrigerant flow during heating operation The EXV H is driven by a 12VDC 2 phase uni polar stepper motor The EXV H has a 475 step range between fully closed and fully open The PCM...

Page 9: ...oor equipment and under charged or over charged systems Sump Heat When the compressor is not running the compressor sump may need to be heated to prevent liquid refrigerant from collecting in the sump...

Page 10: ...e Comm light is On then communication has been received within the last 2 minutes and the equipment is operating in normal communication mode If the Comm light is Off then communication has not been r...

Page 11: ...No code will be displayed if the most recent highest priority diagnostic code occurred more than 240 hours of equipment operating time before entering recall mode No code will be displayed if there ha...

Page 12: ...nd indoor fan for proper operation Low Pressure Protection The equipment monitors suction pressure relative to low pressure limits Low pressure limits are compressor speed and model dependent If the c...

Page 13: ...oil Temperature OCT Thermistor The OCT thermistor provides the coil liquid line temperature to the PCM where it is used primarily for defrost control The OCT thermistor is located on an extension tube...

Page 14: ...dentical Either pressure transducer can connected to either input The software in the PCM detects which transducer is connected to which input and assigns the signals accordingly Signals used by contr...

Page 15: ...s received by PCM If this fault is active inspect PCM to Bluetooth module harness and ensure both ends are fully seated on board header Also inspect and repair any wire damage on harness If no green o...

Page 16: ...This code will be set if fuse 2 is blown or missing on PCM board Fuse 2 only powers the LLS When this fault is active the system will not operate The code will clear once fuse is replaced with new un...

Page 17: ...connections wire damage and wire order This code indicates that the VFD is not able to rotate the compressor rotor enough to complete starting process indicating compressor damage or high pressure dif...

Page 18: ...equired from compressor and VFD The PEV will open 2 5 minutes after compressor shutdown if pressure differential is between 200 300psi or if pressure differential is greater than 50psi and demand is p...

Page 19: ...observed replace sensor If measured resistance is within allowable range replace PCM Code 54 02 ODT Shorted The discharge thermistor is used to protect the compressor and ensure discharge superheat i...

Page 20: ...will operate to a known position as the valve does not have the capability to feedback actual position The PCM software must know the starting point and then count when stepper motor is pulsed At the...

Page 21: ...ill be reduced to 0 If measurement is open replace reactor Otherwise replace VFD Code 81 14 VFD System Fault Unbalanced PFCM Code 81 54 VFD System Lockout Unbalance PFCM Applicable to 4 and 5 ton mode...

Page 22: ...resistance against table Listen to compressor during operating for abnormal noise indicating physical damage VFD may have internal damage causing high current or compressor may be damaged Code 83 57 V...

Page 23: ...with disconnect if malfunction persists replace VFD Code 88 32 VFD Internal Fault IPM Temp Sens The VFD has internal temperature sensors to monitor critical power components and take action if operati...

Page 24: ...ue to operate normally since the only way to correct this fault is to replace VFD Code 88 38 VFD Internal Fault DC Discharge Code 88 78 VFD Lockout Int DC Discharge The unit VFD converts boosts 230VAC...

Page 25: ...55 Compressor Low Discharge Limit 34 11 58 Compressor High Temperature Limit 35 11 58 Compressor High Compression Limit 36 15 55 Compressor Low Compression Limit 38 13 53 Compressor Starting Error 54...

Page 26: ...t Limit 1 Speed Reduction 12 Compressor Current Limit 2 Speed Reduction 15 55 Compressor Current Limit 3 Shutdown 16 56 Compressor Current Limit 4 Shutdown 57 Compressor Underspeed Shutdown 84 11 58 V...

Page 27: ...nd designs without notice and without obligations 27 A200187 Fig 18 2T 3T Control Box A200188 Fig 19 4T 5T Control Box Note 4T VFD similar not exact 5T reactors have additional chokes to meet FCC requ...

Page 28: ...otice and without obligations 28 A200191 Fig 22 2 3T VFD Connections VFD control relay and LED Fan motor connections VFD to PCM comm connection DC DC terminals Fan motor fuse Compressor UVW connection...

Page 29: ...192 Fig 23 4 5T VFD Connections Note 4T uses separate terminals VFD to PCM comm connection Fan motor connections Compressor UVW connections DC DC terminals Reactor connection Filter board input VFD co...

Page 30: ...186CNV 284ANV Service Manual Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 30 A200193 Fig 24 PCM used on all models...

Page 31: ...designs without notice and without obligations 31 A200194 Fig 25 Bluetooth Module used on all models A200195 Fig 26 Fan Motor used on all models A200196 Fig 27 2 3 4T Rector Note 4Tuses 2 reactors A2...

Page 32: ...rer reserves the right to change at any time specifications and designs without notice and without obligations 32 A200199 Fig 30 PCM to Bluetooth Module Comm Cable used on all models A200200 Fig 31 VF...

Page 33: ...186CNV 284ANV Service Manual Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 33 A200201 Fig 32 PCM Wiring Diagram...

Page 34: ...brazing alloy is used on copper to brass copper to steel or copper to copper Flux is required when using silver brazing alloy Do not use low temperature solder 3 Fluxes should be used carefully Avoid...

Page 35: ...flow of refrigerant in system This reversing valve device is easy to troubleshoot and replace The reversing valve solenoid can be checked with power off with an ohmmeter Check for continuity and shor...

Page 36: ...where acid might occur such as burnout Heat pump units must have the drier installed between the compressor and accumulator only Remove after 10 hours of operation Never leave suction line filter drie...

Page 37: ...l eventually fail from lack of lubrication If bleed hole is plugged accumulator must be changed The accumulator has a fusible element located in the bottom end bell See Fig 37 This fusible element wil...

Page 38: ...igerant is leaking at that point A simple and inexpensive method of testing for leaks is to use soap bubbles See Fig 40 Any solution of water and soap may be used Soap solution is applied to all joint...

Page 39: ...ngthen careers and businesses We believe in providing high quality learning experiences both online and in the classroom Access My Learning Center with your HVACpartners credentials at www mlctraining...

Page 40: ...Company Edition Date 06 20 Catalog No SM186CNV 284ANV 01 Replaces NEW 186CNV 284ANV Service Manual Manufacturer reserves the right to change at any time specifications and designs without notice and...

Reviews: