PSI BOX PLUS+ Reference
Control Functions
LOCAL.
Set Some Or All Devices To Local Control.
________
_____________________________________
Purpose.
Commands some or all devices to return to front
__________
panel control.
The LOCAL command is a very flexible way to command
one or more devices to respond to their front panel, local,
controls rather than to the PSI BOX.
If no device address is specified then the PSI BOX drops
both REN and ATN lines false, ALL IEEE bus devices are now
under front panel control. If one or more devices addresses are
given then those devices are commanded to Listen and then told
via the GTL command to respond to their front panel controls
rather than to the PSI BOX controller.
Format.
LOCAL
_________
Params.
None, one or many.
_________
Returns.
None.
__________
Example.
________
_
BUS LOCAL
all devices control by front panel
BUS LOCAL 2,3,4
devices 2,3 & 4 to front panel control
Bus Activity.
___________
_
drop REN
drop ATN
or
assert ATN if not already so
MTA of PSI BOX
UNL all stop listening
LAG 2 first addresses specified
....
LAG 4 last address specified
GTL addressed device to go to local control