Cross-sectional area A of outer conduc‐
tors
Minimum cross-sectional area A
PE
of
equipment grounding connection
A ≤ 16 mm²
A
16 mm² < A ≤ 35 mm²
16
35 mm² < A
A / 2
Fig.5-13:
Equipment Grounding Conductor Cross Section
The line for the connection of the equipment grounding conductor
must have at least the cross section of the mains supply feeder.
With cross sections of the mains supply feeder smaller than
10 mm
2
(AWG 8), the equipment grounding conductor must have
at least 10 mm
2
(AWG 8).
1
Joint bar
2
Connection to equipment grounding system
Fig.5-14:
Equipment Grounding Conductor Connection for Supply via HMV01,
HMV02, HCS03
1
Joint bar
2
Connection to equipment grounding system
Fig.5-15:
Equipment Grounding Conductor Connection for Supply via HCS02
Design, Tightening Torque
The joint bars are connected by means of screws: