With contact bars -072
A
220
Additionally with contact bars ‑042 and end piece
A
245
Fig.5-10:
Function, Pin Assignment, Properties
Fig.5-11:
DC Bus Connection With Contact Bars
Notes on Installation
If in special cases it is not possible to use the contact bars provided to establish
the connection, the connection must be established using the shortest possible
twisted wires.
Risk of damage by reversing the polarity of the
DC bus connections L+ and L-
NOTICE
Make sure the polarity is correct.
Length of twisted wire
Max. 2 m
Line cross section
Min. 10 mm
2
,
but not smaller than cross section of supply feeder
Line protection
By means of fuses in the mains connection
Dielectric strength of single
strand against ground
≥ 750 V (e.g.: strand type – H07)
Fig.5-12:
DC Bus Line
Bosch Rexroth AG
DOK-INDRV*-HMS02*UL***-IB03-EN-P
Rexroth IndraDrive Drive Controllers Power Sections HMS02
36/67
Instructions for Use