Maximum allowed inductance of 100 µH (2 twisted single strands, 75 m
long)
●
Parallel line routing where possible
The input 0V is connected in conductive form to the housing po‐
tential. It is therefore impossible to use an insulation monitor at
+24V and 0V against housing.
5.2.6
L+ L-, DC Bus Connection
Lethal electric shock caused by live parts with
more than 50 V!
WARNING
Before working on live parts: De-energize the installation and secure the power
switch against unintentional or unauthorized re-energization.
Wait at least 30 minutes after switching off the supply voltages to allow dis‐
charging. To shorten the waiting time until voltage has fallen below 50 V, you
can use a discharging device (see chapter "Appendix").
Check whether voltages have fallen below 50 V before touching live parts!
Function, Pin Assignment
The DC bus connection connects
●
several drive controllers to one another
●
a drive controller to additional components
HCS02.1E-W0012 drive controllers do not have a DC bus connec‐
tion.
Technical Data of the Connection Point
View
Identifica‐
tion
Function
L+
Connection points for connecting DC bus connections
L-
Screw connection
M6 thread at device (terminal block)
Unit
Min.
Max.
Tightening torque
Nm
5,5
6,5
Short circuit protection
Via fusing elements connected in the incoming circuit to the
mains connection
Overload protection
Via fusing elements connected in the incoming circuit to the
mains connection
Current carrying capacity "looping through" from L+ to L+, L- to L-
(contact bars in scope of supply of accessory HAS01)