4.3.3
Cables
Motor power cable
When selecting the motor power cable, observe the following:
●
Cross section: The minimum size depends on the type current and rout‐
ing method of the motor power cable.
●
Leakage capacitance: Without HLL DC bus choke, maximum 500 nF
per phase is permitted (phase: HMU + HNL + HNC + HNL + HNF).
When connecting multiple HMUs in parallel, the allowed leakage capaci‐
tance drops to 450 nF per phase. Reason: balancing HNF mains filter.
The overall leakage capacitance for n parallel HMUs is therefore n x 450
nF.
Encoder cables
Encoder
Allowed cable length
Encoder evaluation in CSx02 control sec‐
tion
75 m
Tab. 4-4:
Cable length
Bosch Rexroth AG
DOK-INDRV*-HXX05******-PR02-EN-P
52/407
Rexroth IndraDrive ML Drive Systems with HMU05
Combining the individual components