Country of use: international except for USA/Canada
Fuse I
N
[A]
Current carrying ca‐
pacity (× 0.87) I
Z(40)
[A]
Cross section A [mm
2
]
Installation type E
1 ×
2 ×
3 ×
16
10.4
16
16
12.4
16
20
16.10
1.5
25
21.75
2.5
35
29.58
4
50
37.41
6
63
52.20
10
80
69.60
16
100
87.87
25
125
109.62
35
160
133.11
50
200
170.52
70
250
207.06
95
315
240.12
120
355
277.53
150
400
316.68
185
425
374.10
240
500
432.39
300
160
272.83
2 x 70
200
331.30
2 x 95
250
384.19
2 x 120
250
444.05
2 x 150
315
506.69
2 x 185
400
598.56
2 x 240
400
691.82
2 x 300
160
358.09
3 x 70
200
434.83
3 x 95
200
504.25
3 x 120
250
582.81
3 x 150
250
665.03
3 x 185
315
785.61
3 x 240
400
908.02
3 x 300
Tab. 11-3:
Line cross sections and fuses, E according to EN 60204-1:2006, Ta‐
ble 6, for 150mm² and more DIN IEC 60364-5-52:2004, Table B.
52-10
Bosch Rexroth AG
DOK-INDRV*-HXX05******-PR02-EN-P
374/407
Rexroth IndraDrive ML Drive Systems with HMU05
Appendix