![Bosch Rexroth HMU05.1N Series Project Planning Manual Download Page 374](http://html.mh-extra.com/html/bosch/rexroth-hmu05-1n-series/rexroth-hmu05-1n-series_project-planning-manual_44851374.webp)
Country of use: international except for USA/Canada
Fuse I
N
[A]
Current carrying ca‐
pacity (× 0.87) I
Z(40)
[A]
Cross section A [mm
2
]
Installation type B1
1 ×
2 ×
3 ×
400
342.78
300
160
238.03
2 × 70
160
288.14
2 × 95
200
332.69
2 × 120
200
364.70
2 × 150
250
412.03
2 × 185
315
481.63
2 × 240
315
548.45
2 × 300
125
312.42
3 × 70
160
378.19
3 × 95
160
436.65
3 × 120
200
478.67
3 × 150
200
540.79
3 × 185
250
632.14
3 × 240
315
719.84
3 × 300
Tab. 11-1:
Line cross sections and fuses, B1 according to EN 60204-1:2006,
Table 6, for 150mm² and more DIN IEC 60364-5-52:2004, Table B.
52-4
International except for USA/
Canada; installation type B2
Country of use: international except for USA/Canada
Fuse I
N
[A]
Current carrying ca‐
pacity (× 0.87) I
Z(40)
[A]
Cross section A [mm
2
]
Installation type B2
1 ×
2 ×
3 ×
2
1.6
0.75
4
3.3
0.75
6
5.0
0.75
10
8.5
0.75
16
10.1
1.0
16
13.05
1.5
20
17.40
2.5
25
23.49
4
35
29.58
6
50
40.02
10
63
53.94
16
80
69.60
25
Bosch Rexroth AG
DOK-INDRV*-HXX05******-PR02-EN-P
372/407
Rexroth IndraDrive ML Drive Systems with HMU05
Appendix