110
en | Replacing a Power-Fan Canister in the Controller-Drive Tray
E2600 DSA E-Series iSCSI Disk Arrays
- | V2 | 2012.09
Installation Manual
Bosch Security Systems
19. Based on the LED status, perform one of these actions:
–
The Power-Fan Input DC Power LED and the Power-Fan Output DC Power LED are
on and the Power-Fan Service Action Required LED is off
Go to step 21.
–
The Power-Fan Input DC Power LED and the Power-Fan Output DC Power LED are
off and the Power-Fan Service Action Required LED is on
Check that the power-fan canister has been installed correctly. Reinstall the power-
fan canister if necessary. Go to step 20.
20. Did this action correct the problem?
–
Yes
Go to step 21.
–
No
If the problem is not resolved, contact your Customer and Technical Support repre-
sentative.
21. Complete any remaining Recovery Guru procedures, if needed.
22. Using the LEDs and the storage management software, check the status of all of the trays
in the storage array.
23. Does any component have a Needs Attention status?
–
Yes
Click the
Recovery Guru
toolbar button in the Array Management Window, and com-
plete the recovery procedure. If the problem is not resolved, contact your Customer
and Technical Support representative.
–
No
Go to step 24.
24. Remove the antistatic protection.
25. Create, save, and print a new storage array profile.