Day mode
Notice!
Depending on the security level in question, not all detectors can be switched to day mode.
Depending on the configuration, a distinction is made between the following possible alarm
delays in day mode:
–
Alarm verification
–
Pre-alarm
A pre-alarm is displayed for the following alarm delays:
–
Intermediate alarm storage
–
Dual-detector dependency
–
Dual-zone dependency
For a detailed description of the various alarm delays, see Entry delays.
–
Internal alarm
An alarm that is reported to the panel in day mode. No transmission devices to the fire
department are activated.
8.4
Alarm message to the panel
The following description has been written on the basis of a sample fire alarm message.
8.4.1
Optical and acoustic signals
–
The LED alarm icon
lights up red.
–
An internal buzzer sounds; see also
Silence internal buzzer, page 41.
–
Depending on the configuration, sounders and/or visual notification appliances (e.g.
sirens, strobes) are activated.
If the transmission device to the fire department is activated, the
LED icon lights up red.
8.4.2
Displaying the detector zones in alarm state
The number of messages in question is displayed on the status bar.
Notice!
First of all, the logical zones in which one or more detectors have triggered an alarm are
listed. To display the individual detectors, select the logical zone you require. See also
Displaying the individual detectors in a logical zone, page 38.
The individual messages are shown in the display:
–
List fields with white background: unacknowledged alarm messages
–
List fields without distinction: acknowledged alarm messages
Logical Zones
Notice!
A maximum of four alarm messages can be displayed on the display simultaneously. Only
fields that can be operated are displayed (e.g.
Acknowledge
and
Reset
).