to reset all elements that have triggered a fire alarm, for example
–
Logical zone
a list of the logical zones is displayed
–
Detector
a list of the detectors is displayed
To reset an alarm message, select either
–
Reset
on the message display
or
–
The alarm message and
Reset
in the detailed view:
Depending on the variant that is offered (see above), all elements that are not in the
alarm state or all types of message within the same message type are reset.
If different elements are offered for resetting:
1.
Select an element. At the menu items Zone and Detector, a list with all the logical zones
and detectors concerned appears.
2.
Select the list field you require. Refer to
Scrolling through lists, page 25 for information
on how to scroll forward and backward through a list.
The list field is marked.
3.
Select
Reset
.
The selected element / element group is reset.
TEXT
R
If a list field is marked with an R, the process of resetting is not yet complete for this element.
If an element cannot be reset, it will continue to be displayed in the list.
After the successful resetting of all elements, the standby display is displayed.
9.9
Bypassing detectors
To bypass a detector that has triggered an alarm:
1.
Select the alarm message you require.
2.
Select
Bypass
.
Notice!
The system does not transmit any information as to whether it was possible to bypass the
selected element. To monitor the operation, please check the element.