Notice!
To avoid the panel running into a safe state, do not reboot the panel twice within 100
seconds.
If the panel reboots twice within 100 seconds (either because of a system error or
intentionally for example during the initial set-up) it runs into a safe state which can be ended
by a manual restart only. A warning tone sounds and a message appears on the screen. In this
case, please follow the instructions on the display.
5.2
Initial setup
When you start the panel for the first time, you must perform the following steps:
Calibrate touch screen
When initially starting the panel, first of all you must calibrate the touch screen:
1.
Switch on the panel by applying power or pressing the power button. The touchscreen
calibration procedure will start automatically if required.
2.
Perform the calibration by following the instructions on the screen.
The boot process will automatically continue after the calibration was completed.
Set time and date
Touch the field you require and enter the correct value. For details see
Set physical node address (PNA/RSN)
You must set the physical node address (PNA/RSN) when switching on the panel for the first
time.
Notice!
There are no mechanical rotary switches.
The physical node address must be identical with the number configured in the programming
software. After a change of the physical node address, a reboot of the panel is required.
To change the physical node address enter a number between 1 and 64. Choose
OK and
reboot
to make the change effective.
Use Ethernet settings
Check
Use Ethernet settings
if the panel is used within an Ethernet network.
!
Caution!
If you check
Use Ethernet settings
it is absolutely necessary to set the panel IP address via
Configure Ethernet
.
Use RSTP
Check
Use RSTP
to activate Ethernet redundancy. For details see Ethernet redundancy.
Configure Ethernet
Check
Configure Ethernet
to use the standard IP address of the panel.
Reboot
After having made all the necessary settings, reboot the panel by pressing
Reboot
.