FPA-5000 | FPA-1200 | AVENAR panel 8000 |
AVENAR panel 2000 | AVENAR keypad 8000
Maintenance – walktest | en
65
Bosch Sicherheitssysteme GmbH
User Guide
2020-07 | 3.0 | F.01U.378.877
15
Maintenance – walktest
Notice!
Terminology
The term
Walktest
, which is used in the fire panel and in the documentation, corresponds to
the EN54‑2 standard term
Test condition.
This chapter contains information about the following points:
–
–
Starting and ending walktest, page 67
–
Ending walktest for all elements, page 68
–
Displaying tested or untested elements, page 68
–
Assigning tested elements to a walktest group, page 68
A walktest is indicated by a yellow LED display on the panel.
!
Caution!
Alarm or fault messages from detectors switched to walktest are not forwarded to
transmission devices or extinguishers.
Notice!
If a signaling device is activated during a walktest, it emits a different signal tone to the one it
emits in the alarm state.
15.1
Walktest groups
The following options are available for switching elements to walktest:
–
Select individual elements from lists and/or
–
Select previously defined walktest groups consisting of at least one element.
There are 12 pre-defined walktest groups. The number of possible walktest groups is
predefined: January to December.
Example:
Detectors which are to be tested in May, can be grouped together in a group called May.
New elements can be added to a group, and elements that have already been added can be
removed.
Notice!
Even if the elements in a group (e.g. January) have been completely deleted, this group will
still be displayed in the list.
15.1.1
Adding or deleting elements
In order to add elements to a walktest group or remove elements from it:
1.
In the start menu, select
Maintenance
2.
Walktest
3.
Create / Change walktest group
A list of the walktest groups is displayed.
4.
Select a walktest group, e.g. February.
You can choose from a number of options:
–
Delete all
: Delete all elements in the selected group.