FPA-5000 | FPA-1200 | AVENAR panel 8000 |
AVENAR panel 2000 | AVENAR keypad 8000
Maintenance – walktest | en
67
Bosch Sicherheitssysteme GmbH
User Guide
2020-07 | 3.0 | F.01U.378.877
In order to add new elements:
1.
Select
New
.
The display changes. Various element categories containing elements which have not
been assigned to any walktest group yet are displayed.
2.
Select the element category you require.
3.
Select one or more list fields.
The list fields are marked.
4.
Select
Add
.
The selected element is added to the selected walktest group.
Change name
To change the name of the input or output group:
1.
Entering numbers and text, page 27.
2.
Select
OK
.
The new name is confirmed.
15.2
Starting and ending walktest
Notice!
The information about the date and time of every walktest is stored in the history log. You can
print this information on a printer. See
Maintenance – history log, page 69.
15.2.1
Starting the walktest
To select the elements for the walktest and to switch them to walktest:
1.
In the start menu, select
Maintenance
2.
Walktest
3.
Start / End walktest
Various element categories are displayed.
4.
Select:
–
More...
to display further categories or
–
one of the displayed categories or
–
Select by number
and enter the number of the element into the search screen; see
Search Function/Element, page 26.
Notice!
If you select the element category
Loop
,
Logical zone
,
Detector
or
Walktest group
, you will
be asked to select the type of walk test. Select
Sequential walktest
to check each individual
sensor (optical, chemical or thermal) of the detectors you are testing, or select
Simultaneous
walktest
to test combination detectors using a test device with combined trigger substances
for simultaneous testing of multiple sensors.
Example:
1.
Select
Walktest group
.
2.
Select
Sequential walktest
or
Simultaneous walktest
A list of walktest groups is displayed. Refer to
Scrolling through lists, page 25 for
information on how to navigate through a list.
3.
Select the list field you require.
The field is marked.
4.
Select
On
.
The selected walktest group is switched to walktest.