Frequency inverter
Asynchronous motor or synchronous motor
(shielded) mains cable
Shielded control cables
Metal mounting plate
In addition to the components listed above, a precharging circuit must be provided.
Line choke
Install the line choke between the radio interference filter and the feed-back unit.
Install another line choke between the radio interference filter and the drive inverter.
Radio interference filter
The Load terminal of the radio interference filter is to be wired to the mains unit side, the Line
terminal to the mains side.