Key
Meaning
01
Interior temperature too low, check control cabinet heating.
Output current
F05
00
Overloaded, check load situation and ramps.
01
Instantaneous output current value too high. Check load.
02
Dyn. Phase-Current Limitation Check load.
04
Overloaded, check load situation and current value limit controller.
DC-Link Voltage
F07
00
DC link voltage too high, check deceleration ramps and connected brake resistor.
01
DC link voltage too low, check mains voltage.
02
Mains failure, check mains voltage and circuit.
03
Phase failure, check mains fuse and circuit.
05
Brake chopper
Trigger threshold
506 too small, check mains voltage.
Electronic voltage
F08
01
Electronics voltage DC 24 V too low, check control terminal.
04
Electronic voltage too high, check wiring of control terminals.
Output frequency
F11
00
Output frequency too high, check control signals and settings.
01
Max. frequency achieved by control, check deceleration ramps and connected brake resistor.
10
Overfrequency. See application manual "Hoisting Gear Drives".
Modbus and VABus
F20
10
Communication error according to parameter
CM: VABus Watchdog Timer
413.
CANopen
F20
21
CAN Bus OFF
22
CAN Guarding
23
Error state
24
SYNC error (SYNC timing)
25
CAN error state
26
RxPDO1 length error
Number of received bytes differs from mapping.
27
RxPDO2 length error
28
RxPDO3 length error
2A
CAN RxPDO1 Timeout
2B
CAN RxPDO2 Timeout
2C
CAN RxPDO3 Timeout
System Bus
F21
nn
Malfunction message in system bus master with malfunction in system bus slave
nn = node ID of slave (hex)
F22
00
Communication fault, system bus, timeout Sync telegram
01
Communication fault, system bus, timeout RxPDO1
02
Communication fault, system bus, timeout RxPDO2
03
Communication fault, system bus, timeout RxPDO3
10
Communication fault, system bus, bus Off