Operating Instructions AEC
29
6
Technical data
6.1
Rating plate
Type designation
AEC-401-21
Nominal voltage
401 = 400 V
Recommended power
Part number & serial number
Warning! Components sensitive
to electrostatic discharge.
Warning! High leakage current.
Warning! Dangerous voltage. Danger of electric
shock.
Warning! Hot surfaces.
[1] Marking for UL508c (where applicable).
6.2
General technical data
CE conformity
The AEC mains unit meet the requirements of the Low Voltage Directive 2006/95/EEC
and EN 50178 / DIN VDE 0160 and EN 61800-2.
EMC directive
For proper installation of the mains unit in order to meet the requirements of
EN 61800-3, please comply with the installation instructions in these Installation
Instructions.
Interference immunity
The AEC mains unit meets the requirements of EN 61800-3 for use in industrial
environments.
UL Approval
The frequency inverters are also marked with the UL label according to UL508c,
which proves that they also meet the requirements of the CSA Standard C22.2-No.
14-95.
Ambient temperature
Operation: 0…55 °C; as from 40 °C power reduction should be considered.
Environmental class
Operation: 3K3 (EN60721-3-3)
Relative humidity 15…85%, no water condensation
Ingress protection rating IP20 if covers and connection terminals are used properly.
Altitude of installation
Up to 1000 m at nominal specifications.
Up to 4000 m at reduced power.
Storage
Storage according to EN 50178.
Bonfiglioli Vectron recommends that the unit be connected to nominal voltage for 60
minutes after one year, at the latest.
Overload capacity
Continuous operation 100% I
N
Up to 150% I
N
for 60 s
Up to 200% I
N
for 1 s
Overload capacity can be used every 10 minutes.
Parameterization
Freely programmable digital inputs and outputs.
Four separate data sets