Output, mains side, at 400 V mains voltage
Output power
kVA
52.0
62.3
76.2
86.6
-
Nominal output current
A
75
90
110
125
-
Voltage
V
320 … 460
Frequency
Hz
45 … 66
Protection
Short circuit / earth fault proof
Switching frequency
kHz
4, 8
Line fuses
-
external
Mechanical
Dimensions
HxWxD
mm
400x275x260
-
Weight approx.
kg
20
20
20
20
-
Conductor cross-section
mm
2
up to 70
up to 70
up to 70
up to 70
-
Ingress protection rating
-
IP20 (EN60529)
Form of assembly
-
vertical
Ambient conditions
Coolant temperature
°C
0 … 40 (3K3 DIN IEC 721-3-3)
Storage temperature
°C
-25 … 55
Transport temperature
°C
-25 … 70
Rel. humidity
%
15...85, not condensing
DC-link
DC nominal current
A
90
109
132
152
-
Max. DC input voltage
VDC
Overvoltage shutdown at >800 VDC
Output current
Output power
Switching frequency
4 kHz
8 kHz
12 kHz
16 kHz
52.0
kVA
75.0 A
75.0 A
-
-
62.3
kVA
90.0 A
90.0 A
-
-
76.2
kVA
110.0 A
110.0 A
-
-
86.6
kVA
125.0 A
125.0 A
-
-