In mains unit mode, a central DC-link can be powered via the AEC mains unit. The cables
in the DC-link of the connected frequency inverters are to be fused properly. When
dimensioning the DC-fuses, the derating factors specified by the fuse manufacturer must
be considered in addition to the specified DC-link voltage setpoint.
Mains unit
Type
AC mains nominal current [A]
DC nominal current[A]
AEC 401-19
14
17
AEC 401-21
18
19
AEC 401-22
22
27
AEC 401-23
25
31
AEC 401-25
32
39
AEC 401-27
40
47
AEC 401-29
45
53
AEC 401-31
60
71
AEC 401-33
75
90
AEC 401-35
90
109
AEC 401-37
110
132
AEC 401-39
125
152
AEC 401-43
150
181
AEC 401-45
180
217
AEC 401-47
210
253
AEC 401-49
250
301
AEC 401-51
305
366
AEC 401-53
380
456
AEC 401-55
475
570
AEC 401-57
595
714
AEC 401-59
645
774
AEC 401-61
735
882
6.7.2
Line choke
Line chokes reduce mains harmonics and reactive power. In addition, a longer service life of the device is
possible. When using a line choke, note that line chokes may reduce the maximum output voltage of the
device.
The line choke must be installed between the mains connection and the input filter.
Mains unit/feed-back unit
Line choke
Type
AC mains current [A]
Part number
Inductance [mH]
AEC 401-19
14
184 420 015
1.95
AEC 401-21
18
184 420 018
1.63
AEC 401-22
22
184 420 025
1.17
AEC 401-23
25
AEC 401-25
32
184 420 034
0.86
AEC 401-27
40
184 420 050
0.59
AEC 401-29
45
AEC 401-31
60
184 420 060
0.49
AEC 401-33
75
184 420 075
0.37
AEC 401-35
90
184 420 090
0.33
AEC 401-37
110
184 420 115
0.25
AEC 401-39
125
184 420 135
0.22
AEC 401-43
150
184 420 160
0.18
AEC 401-45
180
184 420 180
0.16
AEC 401-47
210
184 420 210
0.14
AEC 401-49
250
184 420 250
0.12
AEC 401-51
305
184 525 280
0.105