5 Commissioning

The compressor is already thoroughly
dehydrated, tested for leaks and
under pressure with holding charge
(N

2

).

Attention!
Test the strength pressure and
the tightness of the entire plant
preferably with dry nitrogen (N

2

).

Compressor must be put out of
circuit when using dried air –
keep the shut-off valves closed.

Gefahr!
By no means the compressor
may be pressure tested with
oxygen or other industrtial
gases!

Warning!
Never add refrigerant to the test
gas (N

2

or air) – e. g. as leak

indicator.
Critical shift of the refrigerant
ignition limit with high pressure
possible!
Environmental pollution with
leakage or when deflating!

5.1 Strength pressure test

Evaluate the refrigerant circuit (as-
sembly) according to EN 378-2 (or
valid equivalent safety standards). The
compressor had been already tested
in the factory for strength pressure.
Therefore a tightness test (5.2) is suf-
ficient.

However, if the whole assembly is test-
ed for strength pressure:

Danger!
Test pressure shall not exceed
the maximum operating pres-
sures indicated on the name
plate!
If necessary leave the shut-off
valves closed!

5.2 Tightness test

Evaluate tightness of the entire refrig-
erant circuit (assembly) or parts of it –
according to EN 378-2 (or valid equiv-
alent safety standards) by using pre-
ferably an overpressure of dry nitro-
gen.

!

!

!

5 Mise en Service

Le compresseur est soigneusement
séché en usine, son étanchéité est
contrôlée et il est rempli avec un gaz de
protection (N2).

Attention!
Essayer la résistance à la pression
et l'étanchéité de toute l’installation
préféremment avec l'azote sec (N

2

).

Compresseur doit être remis hors
du circuit quand l'air sec est vitilisé.
– maintenir les vannes d’arrêt fer-
mées.

Danger !
Ne faire, en aucun cas, les essais
de pression sur le compresseur
avec de l'oxygène ou tout autre gaz
technique ! 

Avertissement !
Ne jamais ajouter fluide frigorigène
au gaz d'essai (N

2

ou air) – par ex.

comme indicateur de fuite.
Décalage critique de la limite d’in-
flammabilité du fluide frigorigène
possible, en cas de surpression !
Pollution de l'environnement en 
cas de fuite ou d’évacuation du 
système !

5.1 Essayer la résistance à la pression

Essayer le circuit frigorifique (groupe as-
semblé) correspondant à EN 378-2 (ou
normes de sécurité équivalentes, qui sont
valables). Le compresseur était déjà
essayé à l'usine sur son résistance à la
pression. Par ça un essai d'étanchéité
(5.2) est suffisiant.

En cas d'essayer néanmoins la résistance
à la pression du tout le groupe assemblé:

Danger !
Le timbrage ne doit pas excéder 
les pressions de service maximales
qui sont marquées sur la plaque
d'identité !
En cas utile maintenir les vannes
d'arrêt fermées !

5.2 Essayer l'étanchéité

Essayer tout le circuit frigorifique (groupe
assemblé) ou des parties – conformé-
ment à EN 378-2 (ou normes de sécurité
équivalentes, qui sont valables). Utiliser
préféremment une surpression avec de
l'azote séché.

!

!

!

5 In Betrieb nehmen

Der Verdichter ist ab Werk sorgfältig
getrocknet, auf Dichtheit geprüft und
mit Schutzgas (N

2

) befüllt.

Achtung!
Druckfestigkeit und Dichtheit der
gesamten Anlage bevorzugt mit
getrockneten Stickstoff (N

2

) prü-

fen.
Bei Verwendung von getrockne-
ter Luft Verdichter aus dem
Kreislauf nehmen –
Absperrventile unbedingt
geschlossen halten.

Gefahr!
Verdichter darf keinesfalls mit
Sauerstoff oder anderen techni-
schen Gasen abgepresst wer-
den! 

Warnung!
Dem Prüfmedium (N

2

oder Luft)

keinesfalls Kältemittel beimi-
schen – z. B. als Leck-Indikator.
Kritische Verschiebung der
Kältemittel-Zündgrenze bei
Überdruck möglich!
Umweltbelastung bei Leckage
und beim Abblasen!

5.1 Druckfestigkeit prüfen

Kältekreislauf (Baugruppe) entspre-
chend EN 378-2 prüfen (oder gültigen
äquivalenten Sicherheitsnormen). Der
Verdichter wurde bereits im Werk
einer Prüfung auf Druckfestigkeit
unterzogen. Eine Dichtheitsprüfung
(5.2) ist deshalb ausreichend.

Wenn dennoch die gesamte Baugrup-
pe auf Druckfestigkeit geprüft wird:

Gefahr!
Prüfdruck des Verdichters darf
die maximal zulässigen Drücke
nicht überschreiten, die auf dem
Typschild genannt sind!
Bei Bedarf Absperrventile
geschlossen halten!

5.2 Dichtheit prüfen

Kältekreislauf (Baugruppe) als Gan-
zes oder in Teilen auf Dichtheit prüfen
– entsprechend EN 378-2 (oder gülti-
gen äquivalenten Sicherheitsnormen).
Dazu vorzugsweise mit getrocknetem
Stickstoff einen Überdruck erzeugen.

!

!

!

Summary of Contents for 4NFC

Page 1: ...y if they have been installed in these machines according to the existing instruction and as a whole agree with the corresponding provisions of legislation standards to apply refer to Manufacturers De...

Page 2: ...les prescriptions et normes de s curit relatives par ex EN 378 EN 60204 les r gles de s curit g n ralement reconnues les directives de l UE la r glementation du pays concern Les indications de s curit...

Page 3: ...nd mark accessible sec tors Before working on the compres sor Switch off and let cool down For any working at the compressor after the plant has been commis sioned Warning Compressor is under pressure...

Page 4: ...stemperatur Warnung Bei Lufteintritt ggf kritische Verschiebung der K ltemittel Z ndgrenze Lufteintritt unbedingt vermeiden Weitere K ltemittel auf Anfrage R12 hat ein hohes Ozonabbau potenzial und un...

Page 5: ...sor only when engine hood is closed Fasten the compressor either solid at the engine or elastically to the vehicle chassis fig 1 Direct mounting at the engine fig 1a Use spring loaded idler pulley at...

Page 6: ...zen und exakt mit der Antriebsscheibe Spannrolle und Motorachse fluchten Abb 2 Riemenscheiben Magnet kupplungen mit geringst m gli chen Abstand der Spurrillen zum Verdichterlager verwenden Nebenaggreg...

Page 7: ...and shaft at compressor and clutch caused by excessive radial force Do not exceed the recommen ded pretension consultation with BITZER is recommended Dans le cas d un entra nement appropri la force r...

Page 8: ...m 3 3 Montage de l embrayage lectro magn tique Attention Serrer les vis et les crous avec le couple de serrage requis Attention N utiliser que des embrayages qui ont l agr ment de BITZER 4UFC Y 6TFC Y...

Page 9: ...n various positions for connections see pages 12 13 Glisser la poulie au dessus des gou jons de l embrayage et fixer avec les crous 7 couple de serrage 25 Nm Attention La poulie doit pouvoir tre tourn...

Page 10: ...e vanne lors du brasage et apr s Temp rature de brasage maximale 700 C Tuyauteries D une mani re g n rale on ne doit utiliser que des tubes des flexibles et des compo sants propres et secs l int rieur...

Page 11: ...valve parts must be fitted in place of the sealing flanges before the compressor is eva cuated Mounting can be performed at the factory if desired Retrofit requires exchange of the cylinder head A pin...

Page 12: ...einf ll Stopfen 5 lsumpfheizung Option 6 lablass Magnetschraube lfilter 7 ltrockner Option 8 ldruck Anschluss 9 Schauglas Connection positions 1 High pressure connection HP 2 Discharge gas temp sensor...

Page 13: ...l connection and informa tion on operational testing see KT 170 Crankcase heater optional ensures the lubricity of the oil even after long standstill periods It pre vents increased refrigerant solutio...

Page 14: ...n Pollution de l environnement en cas de fuite ou d vacuation du syst me 5 1 Essayer la r sistance la pression Essayer le circuit frigorifique groupe as sembl correspondant EN 378 2 ou normes de s cur...

Page 15: ...mpressor oil level Do not switch on the compressor Charge liquid refrigerant directly into the condenser resp receiver After commissioning it may be nec essary to add refrigerant Charge the refrigeran...

Page 16: ...haute et basse pression Vannes d arr t ouvertes 5 6 Le d marrage Lubrification contr le de l huile Danger Les cheveux les mains ou les v te ments peuvent tre happ s par le mouvement des courroies ou...

Page 17: ...ust be checked for abnormal vibrations If necessary take suitable measures Attention Pipe fractures and leakages at compressor and other com ponents of the plant possible Avoid strong vibrations Switc...

Page 18: ...us les organes de surveillance du compres seur voir chapitre 4 La tension initiale des courroies apr s la p riode de rodage V rifier les vissages et les raccords des c bles lectriques sur ajustement s...

Page 19: ...e tic clutch keep exactly to the instructions of the manufacturer Removal example for LINNIG clutch LA16 see also fig 4 De energize compressor and have it cooled down to at least 40 C Remove V belts S...

Page 20: ...nouvel le garniture d tanch it environ 250 heures les fuites d huile risquent d tre plus importantes Influences nuisibles sur la garniture d tanch it Surchauffe des gaz aspir s trop faible en particul...

Page 21: ...en dehors des plages d applications et y rem dier Recommendation Remplacer l huile et le d shydrateur d huile et nettoyer le filtre huile et le bouchon magn tique environ tous les 3 ans resp apr s 10...

Page 22: ...ors servi ce Fermer les vannes d arr t sur le compres seur Evacuer le fluide frigorig ne Ne pas le laisser chapper mais le r cup rer et le recycler de fa on adapt e Avertissement Le compresseur peut t...

Page 23: ...23 KB 540 3...

Page 24: ...n Subject to change Toutes modifications r s rv es 06 06 80420701 Bitzer K hlmaschinenbau GmbH Eschenbr nnlestra e 15 71065 Sindelfingen Germany fon 49 0 7031 932 0 fax 49 0 7031 932 146 147 www bitze...

Reviews: