INSTALLATION, OPERATION AND MAINTENANCE MANUAL 

 

BiSolid Saver                                                                                        OM-BSSV00/08/2012/EN 

15 

 

 
The main advantages of the boilers from series BiSolid Saver 

А

 are: 

 

  The pellet burners from series BiSolid GP are fully automated – ignition, flame control, 

combustion  chamber  blowing.  Also  equipped  with  intuitive  LCD  display  for  easy 
operation. 

  Automatic  adjustment  of  fresh  air  and  fuel  feed  rates  according  to  the  selected 

operating  temperature,  which  feature  provides  high  efficiency  of  the  appliance  at 
minimum fuel consumption.   

  The  combustion  chamber  is  made  of  fire  resistance  steel,  which  guarantees  reliable 

and long-term operation. 

  Automatic  modulation  of  the  burning  process,  decreasing  the  number  of  stops  and 

ignitions, respectively fuel and electricity consumption. 

  Possibility for wide range regulation of the heat carrier (water) temperature. 

  Possibility for operation with room thermostat and weekly programmer.  

  Circulations pump control according to heat carrier (water) temperature. 

  Possibility for control of extractor fan. 

  Self operation optimization depending on the building inertia (heating losses).  

  Quiet operation and low electric power consumption. 

  Protection from back-fire and heat carrier (water) freezing. 

 
 

 

Warning 
Boilers from series BiSolid Saver W, BiSolid Saver 

С

 and BiSolid Saver 

А

 are 

not designed for firing any type of coal. 

 

Summary of Contents for Saver A

Page 1: ...NSTALLATION OPERATION AND MAINTENANCE MANUAL BiSolid Saver 31 1 2013 09 12 OM BSSV00 08 2012 EN MANUAL FOR INSTALLATION OPERATION AND MAINTENANCE OF HOT WATER SOLID FUEL BOILER FROM SERIES BISOLD SAVE...

Page 2: ...R LONG TERM SWITCH OFF 24 5 6 BOILER HANDLING 25 5 7 BOILER CLEANING AND MAINTENANCE 25 5 8 BOILER REPAIR 26 5 9 WARRANTY AND WARRANTY CONDITIONS 27 5 10 BOILER PACKAGE KIT AT DELIVERY 27 6 BOILER OPE...

Page 3: ...its accessories operate under variable electricity 220 230 V Improper electrical installation or repair may endanger user s life from electrical shock Installation works must be performed only by qual...

Page 4: ...functioning safe and long term operation of the appliance a regular check ups and prophylaxis must be performed at least once per year Such technical care guarantees your investment Repairs should be...

Page 5: ...are led to the flue pipe Under the combustion chamber and the fuel loading tank is situated a two component grill which can be easily controlled with a lever on the boiler side The primary air is sup...

Page 6: ...sh cleaning door 6 Pipes to DBV1 not standard part of the boiler delivery kit 7 DBV1 two way cooling safety valve not standard part of the boiler delivery kit 8 TRV temperature valve regulating the bo...

Page 7: ...turbolators position 6 Rear section 7 Hot water outlet 8 Flue pipe 150 mm 9 Isolation cover 10 Fireclay bricks 11 Cold water inlet 12 Draining muff 13 Cleaning cover 14 Bushes for legs 15 Bottom isol...

Page 8: ...competitor boilers is achieved due to the steel made three pass construction of the heat exchanger finishing with two sets of steel tubes larger heat exchanging area The boilers are suitable for heat...

Page 9: ...INSTALLATION OPERATION AND MAINTENANCE MANUAL BiSolid Saver OM BSSV00 08 2012 EN 9 Figure 4 Standard equipment of the boilers from series BiSolid Saver W...

Page 10: ...ion operation and maintenance The boiler complies with the European ecology directives and requirements Developed and designed for easy and quick installation of pellet burner BiSolid GP Technical dat...

Page 11: ...construction of the heat exchanger finishing with two sets of steel tubes larger heat exchanging area Outer view of hot water boiler from series BiSolid Saver is presented in Figure 5 Figure 5 Outer v...

Page 12: ...ortable for installation operation and maintenance The pellet burners from series BiSolid GP are fully automated ignition flame control combustion chamber blowing Also equipped with intuitive LCD disp...

Page 13: ...00 1100 Boiler wide mm 720 720 720 720 Up to this moment the boilers from series BiSolid Saver A have no analogue on the Bulgarian market They are equipped with constantly installed pellet burner BiSo...

Page 14: ...Solid Saver OM BSSV00 08 2012 EN 14 Figure 7 Outer view of hot water boiler BiSolid Saver Standard equipment of the boilers from series BiSolid Saver A is presented in Figure 8 Figure 8 Standard equip...

Page 15: ...e steel which guarantees reliable and long term operation Automatic modulation of the burning process decreasing the number of stops and ignitions respectively fuel and electricity consumption Possibi...

Page 16: ...BiSolid GP Description Dimension Saver 25 Saver 40 Fuel Wood Pellets Wood Pellets Wood pellets category according to EN 14961 2 ENplus A1 ENplus A1 Nominal heating output kW 25 25 40 35 Working press...

Page 17: ...rvention might damage the boiler and possibly the accompanying equipment The service technician initializing the boiler start up for first time must show the customer all of its main components differ...

Page 18: ...not be dangerously hot If there is any leakage from the boiler s heat exchanger or when the heat exchanger is choked up do not try to start the boiler until normal operation conditions are recovered 2...

Page 19: ...The ash should be taken out in fireproof container with cover Danger In case of danger from penetration of flammable vapors or gasses in the boiler room or any activities that may lead to fire or exp...

Page 20: ...ainer When handling or operating please use gloves as protective equipment Danger When installing the boiler and elements for safety and control please do not forget that all installation works must c...

Page 21: ...color no suspended particulates oils and chemically aggressive and corrosive substances and also it should not be acid pH factor must be higher than 7 0 At first place a comprehensive washing of the e...

Page 22: ...tracking the smoke out of the chimney Indication for quality burning is the lack of excessive smoke from the chimney in case it s a fact it means that there is insufficient secondary air in the combus...

Page 23: ...forms on the inside boiler walls which leak into the combustion chamber Because the flue gases condensation point is 65 o C the condensation forms only when there is cooling of the gases in the middl...

Page 24: ...must burn completely by itself over the fire grate 5 4 BOILER SHORT TERM SWITCH OFF After switching off the boiler clean it take out all burned wastes empty its ash box clean the contact surfaces of...

Page 25: ...t and efficiency We recommend that during transition seasons spring autumn the boiler should be fired for short time at full heating output in order to burn the deposits and to dry the chimney Warning...

Page 26: ...ler The yearly maintenance prophylaxis of the boiler must be performed only by authorized technicians before the start of the heating season Before calling the service technicians the user has to prov...

Page 27: ...resent it to the Seller or authorized service company 5 10 BOILER PACKAGE KIT AT DELIVERY All hot water boilers from series BiSolid Saver are delivered fully assembled and functionality tested The ful...

Page 28: ...r covers kit Sealing rope for heat exchanger cover Special requirement for spare parts must be coordinated with the manufacturer Direction When sending spare parts order please point out the boiler ty...

Page 29: ...than a minute you can switch from wood logs to wood pellets and contrariwise The burners from series BiSolid GP can burn wood pellets with diameter 6 8 mm and category of wood pellets according to EN...

Page 30: ...llet burner When operating boilers from series BiSolid Saver A with wood logs the consumers use the constantly installed pellet burner from series BiSolid GP for initial firing of the wood logs placed...

Page 31: ...pellet burner In this case before starting the pellet burner the user must change the position of the fire grates in the combustion chamber as described in Figure 11 Warning When operating with wood...

Page 32: ...ith wood logs please observe the instructions in part 5 6 from the current manual for operation When operating with wood pellets handling of the pellet burner must be performed according to the BiSoli...

Page 33: ...he electrical parts must be performed by authorized person Warning The burner must be connected to the electrical installation of the relevant appliance boiler by observing all safety techiques The ma...

Page 34: ...6 1 2 3 4 5 6 1 2 3 4 5 6 6 5 4 3 2 1 6 5 4 3 2 1 Fresh air Flue extractor optional Pump Ignition Photo sensor Start Back fire Room thermostat Pt 1000 H2O 1100 W X1 X2 X3 X4 X5 F1 2A F2 2A F3 2A F4 2A...

Page 35: ...with wood logs or wood pellets do not interrupt the boiler power supply because the circulation pump must operate until the boiler cools down In all wiring types the circulation pump must always oper...

Page 36: ...INSTALLATION OPERATION AND MAINTENANCE MANUAL BiSolid Saver OM BSSV00 08 2012 EN 36 Figure 15 Control panel with connectors for pellet burner wiring diagram Pt 1000 Connector Communication...

Page 37: ...ely water temperature sensor Pt1000 must be performed according to the scheme presented in Figure 16 Figure 16 Installation of water temperature sensor Warning Installation of the temperature sensor m...

Page 38: ...n for economic and optimum operation of the appliance The boiler has to be chosen with such size that corresponds to the heating losses of the designated building site Choice of a boiler with too high...

Page 39: ...e boiler room Danger Do not put flammable materials over boiler s top side or near it within the safety distance 7 4 CONNECTING THE BOILER TO THE HEATING SYSTEM The BiSolid Saver boiler is designated...

Page 40: ...revent the fuel feeding door to open properly 7 7 BOILER STRUCTURE INSTALLATION OF COVER PANELS Before performing the boiler installation it is necessary to check 1 Equipment a Free equipment covers w...

Page 41: ...8 d Front cover panel position 4 fig 17 has to be installed from its wider fixing side under the low body brackets then fix it with force to the boiler and then fix it to the upper brackets e Installa...

Page 42: ...ortest as possible without shut off devices and with availability for expansion The expansion tank has to be positioned without possibility for heating from sun light 2 Every heating system must be eq...

Page 43: ...ed at least once per year 12 Individual project must be designed for every heating system 13 If optimum expansion tank is chosen then should not be measured more than 60 kPa hydraulic pressure and wit...

Page 44: ...d transportation During transportation and storage the boilers packages and cover panels should not be pressed Danger The boilers should not be moved or transported without using forklifts transport c...

Page 45: ...y draught has an important effect over the boiler heating output its efficiency and life cycle length Recommended chimney heights are presented in Table 7 Table 7 Recommended chimney heights Chimney s...

Page 46: ...operation Read BiSolid GP pellet burner operation manual Unsealed fuel feeding and ash cleaning doors Check sealing ropes correct sealing ropes positioning if necessary replace sealing ropes Boiler s...

Page 47: ...INSTALLATION OPERATION AND MAINTENANCE MANUAL BiSolid Saver OM BSSV00 08 2012 EN 47 Supplier Address City Str Tel Fax http Reserved rights for technical changes...

Reviews: