INSTALLATION, OPERATION AND MAINTENANCE MANUAL
BiSolid Saver OM-BSSV00/08/2012/EN
24
Warning
If decide to install expansion tank (buffer) in order to extend the boiler life cycle
time, then before that you should eliminate the possibility to occur low
temperature corrosion in the fuel passage, by keeping the temperature in the
boiler above the point of condensation 65
o
C. This can be achieved by a mixing
device. If the low temperature corrosion is not being limited the boiler corrodes
and the expansion tank in most cases reduces the boiler body life time, due to
pressure and dynamic loads over the boiler walls. Authorization to install
expansion tanks got only legally approved servicing companies.
Warning
At boiler initial firing condensation appearance is possible. This should not
embarrass the user, because it is normal event – especially when firing wood
with higher water content. The boiler “dries” when it reaches normal operation
mode.
5.3. BOILER SWITCH OFF
We do not recommend to try accelerating the burning process in the boiler. The fuel must burn
completely by itself over the fire-grate.
5.4. BOILER SHORT-TERM SWITCH OFF
After switching off the boiler, clean it, take out all burned wastes, empty its ash-box, clean the
contact surfaces of the feeding door and the ash-box, and after that close boiler’s feeding and
ash-box doors.
5.5. BOILER LONG-TERM SWITCH OFF
When switching the boiler off for long period of time (at the end of the heating season), it must
be completely cleaned from all unburned accumulations (soot, ash and deposits). Otherwise
the accumulation of moisture in the unburned gasses leads to excessive boiler corrosion.
Warning
The boiler can be operated only by adult people who are well introduced with the
current manual for operation.
Switch off the boiler every time when there is any (even momentary) danger by the
presence of flammable or explosive vapors situated in the same room from which
the boiler intakes air for burning (for example painting paint, spraying or laying
molten substances, gas leakage, etc.).
Boiler initial firing with explosive substances is strictly forbidden.
Boiler overheating is forbidden.
The boiler and the chimney have to be completely cleaned at the end of the heating
season. Also grease all hinges, chimney flap mechanism and other moving parts.