INSTALLATION, OPERATION AND MAINTENANCE MANUAL
BiSolid Saver OM-BSSV00/08/2012/EN
44
Hydraulic difference 50 kPa
Increased volume in the entire system:
V = G.v
V = 180 . 0.0355 = 6.39 dm
3
Expansion tank minimum needed volume:
O =1.3 . 6.39 (195 + 50)/50 = 40.7 dm
3
According to the calculated volume for the expansion tank is defined the real volume closest to
the manufactured volumes O =50 dm
3
Warning:
Revision control overview check must be performed to the integrated expansion
tank and hydraulic test must be performed on every nine years.
7.9. TRANSPORTATION AND STORAGE
The boilers for expedition are offered by the manufacturer on a wooden pallet and secured
against moving with cap bolts. The boilers should not be transported in position different from
their base (normal operating position).
It is necessary to ensure at least the minimum conditions for preservation of the boilers during
their storage and transportation.
During transportation and storage the boilers packages and cover panels should not be
pressed.
Danger
The boilers should not be moved or transported without using forklifts, transport
carts or other wheel based transport utilities.
Package liquidation:
The package can be liquidated with the assistance of waste disposal posts or municipal waste
depot.
Appliance liquidation after life-cycle expiration:
The product liquidation (the boiler) can be liquidated with the assistance of waste disposal
posts or municipal waste depot.
7.10. BOILER INSTALLATION TO FLUE OUTLET PIPES
The flue gas outlet pipes can be fixed to the boiler flue by rivets with 5 mm diameter. The
shortest possible variation for outgoing of the flue pipes has to be chosen considered from the
boiler to the chimney, under angle and upwards.
The flue pipe must be led to the chimney and to be stably fixed to the boiler flue, so there is no
accidentally or movement by hand. The flue pipe line should not be longer that 1,5 m and if
possible additional knee joints should not be used. All flue pipe line parts must be