Calibrating and adjusting the temperature and humidity control
11.3.3 Adjusting the temperature controller
1.
Enter the menu “Inp.Val. correct.“
(see steps 1 to 0, chap. 11.3.1).
Configuration 2
Analogue inputs
Analogue outputs
Limit comperators
Donor-functions
Controller
Service Level
Service Level
Inp.Val. correct.
Analogue Inputs
Analogue Outputs
Bin. Inputs
Bin. Outputs
Anal. Inp. mTRON
Anal. Out. mTRON
Bin. Inp. mTRON
Bin. Out. mTRON
Memory Display
↓
Use the buttons
or
to select the menu item
“Analogue Input 1” and confirm with <ENTER>.
Configuration 2
Analogue inputs
Analogue outputs
Limit comperators
Donor-functions
Controller
Service Level
Service Level
Inp.Val. correct.
Analogue input 1
Analogue input 2
Analogue input 3
Analogue input 4
Analogue input 5
Safety controller
↓
Use the buttons
or
to select a menu item and confirm
with <ENTER>. For each menu item a submenu will be
opened.
Use the buttons
,
,
and
to key in the values given
below and confirm with <ENTER>.
State: On
Start value X: 0.0
Start value W: 0.0
End value X: Value of “Analogue Inputs.“/“1.” (e.g.
+20.8) (step 0, chap. 11.3.2).
End value W: Value of reference measuring in-
strument (e.g. +21.6) (step 0, chap. 11.3.2).
Configuration 2
Analogue inputs
Analogue outputs
Limit comperators
Donor-functions
Controller
Service Level
Service Level
Inp.Val. correct.
Analogue input 1
Analogue input 2
Analogue input 3
Analogue input 4
Analogue input 5
Safety controller
Analogue input 1
State
On
Start Value X
+
0.0
Start Value W
+
0.0
End Value X
+
20.8
End Value W
+
21.6
↓
Push <EXIT> to return to the menu “Inp.Val. correct.“
Use the buttons
or
to select the menu item
“Safety controller” and confirm with <ENTER>.
Configuration 2
Analogue inputs
Analogue outputs
Limit comperators
Donor-functions
Controller
Service Level
Service Level
Inp.Val. correct.
Analogue input 1
Analogue input 2
Analogue input 3
Analogue input 4
Analogue input 5
Safety controller
↓
Service Manual KBF (E5.2) 04-2015
127