Parameter Default
Limits
Unit
Description
Ut1
55
15-H01
°C
Water Setpoint in AUTOMATIC mode
Ut2
55
15-H27
°C
Water Setpoint in MANUAL mode
Parameter Default
Limits
Unit
Description
H01
55
15-60
°C
Max Value water Setpoint with PdC
H05
8
-20 -30
°C
Setpoint outdoor air temperature to activate the electrical heater
H07
65
60-70
°C
Thermal shock Setpoint
H08
365
1-365
days
Interval of antibacterial treatment (monthly, weekly, etc.)
H09
3
1-5
Num(1)
Number of repetitions for each treatment cycle
H10
15
15-30
min
Duration of treatment cycle (time of staying at thermal shock temperature)
H11
6
6-24
hours
Time between two cycles
H15
0
-5 -5
°C
Offset probe S1 (input AI1)
H16
0
-5 -5
°C
Offset probe S2 (input AI2)
H18
000
0-255
Num(3)
Manufacturer Password (to access parameter 2°level)
H19
0
0-1
Num(1)
Internal parameter
H20
90
0-255
sec*10
Minimum time between switching off and switching on - Time OFF-ON
H21
100
0-255
sec*10
Minimum time between two successive starts -Time ON-ON
H22
30
0-255
sec
Time for the probe S1 of staying at the set point value
H23
1
0-1
Num(1)
Enable Auto start function [1=enabled]
H26
3
0,0 - 15,0
°C
Differential activation heat pump (Automatic mode)
H27
55
30-70
°C
Value Max water Setpoint (Manual mode)
H28
3
0,0 - 15,0
°C
Differential activation electrical heater (Manual mode)
H29
1
0-1
Number
Enable air probe S2 [0=disabled;1=enabled]
H30
1
0-1
Number
Enabled digital input ID2 [0=disabled;1=enabled]
H32
1
0-1
Num(1)
Enable antibacterial treatment
H33
0
0-1
Num(1)
Enable dynamic setpoint
H34
1
0.5 -2
Num
Slope of the compensation
H35
20
15 - 25
°C
Outdoor air temperature above which the compensation starts
H36
10
5 - 10
°C
Excursion of outdoor air temperature on which the setpoint works
H50
1
1-2
Num(1)
Selection of integrative source [1=Electrical heater; 2=Boiler]
H60
0
0-1
Num(1)
Enable electrical heater ON OFF [0=disabled; 1=enabled]
H70
0
0-1
Num(1)
Enable remote ON OFF [0=disabled; 1=enabled]