77
6
Function
Code
Name
Setting Range
Default
Change
Group FD: Communication
FD-00
Baud rate
Units position (Modbus)
0: 300 bps
1: 600 bps
2: 1200 bps
3: 2400 bps
4: 4800 bps
5: 9600 bps
6: 19200 bps
7: 38400 bps
8: 57600 bps
9: 115200 bps
Tens position (PROFIBUS- DP)
0: 115200 bps
1: 208300 bps
2: 256000 bps
3: 512000 bps
Hundreds position: Reserved
Thousands position: CANlink
0: 20
1: 50
2: 100
3: 125
4: 250
5: 500
6: 1M
5005
✩
FD-01
Modbus data
format symbol
0: No check <8,N,2>
1: Even parity check <8,E,1>
2: Odd parity check <8,O,1>
3: No check, data format <8,N,1>
(Valid for Modbus)
0
✩
FD-02
Local address
0: Broadcast address;
1 to 247
(Valid for Modbus, PROFIBUS-DP and CANlink)
1
✩
FD-03
Modbus response delay
0 to 20 ms (Valid for Modbus)
2
✩
FD-04
Serial port communication
timeout
0.0: Disabled
0.1 to 60.0s
(Valid for Modbus, PROFIBUS-DP and CANopen)
0.0
✩
FD-05
Modbus protocol selection
and PROFIBUS-DP data frame
Units position: Modbus
0: Non-standard Modbus protocol
1: Standard Modbus protocol
Tens position: PROFIBUS-DP
0: PPO1 format
1: PP02 format
2: PPO3 format
3: PPO5 format
30
✩
FD-06
Current resolution read
by communication
0: 0.01A (≤55 kW)
1: 0.1A
0
✩
FD-08
Profibus and CANopen
communication
timeout time
0.0 (Invalid)
0.1 to 60.0s
0
✩