69
6
Function
Code
Name
Setting Range
Default
Change
Group F7: Keypad Operation and Display (continued)
F7-07
Heatsink temperature
of AC Drive
-20°C to 120°C
—
•
F7-08
Product number
—
—
•
F7-09
Accumulative running time
0h to 65535h
—
•
F7-10
Performance software version
—
—
•
F7-11
Function software version
—
—
•
F7-12
Number of decimal places for
load speed display
Units position: Number of decimal places
for U0-14
0: No decimal place
1: One decimal places
2: Two decimal places
3: Three decimal places
Tens position: Number of decimal places
of U0-19/U0-29
1: One decimal places
2: Two decimal places
21
✩
F7-13
Accumulative
power-on time
0 to 65535 h
—
•
F7-14
Accumulative power
consumption
0 to 65535 kWh
—
•
Group F8: Auxiliary Functions
F8-00
Jog frequency reference
0.00 Hz to max. frequency
2.00 Hz
✩
F8-01
Jog acceleration time
0.0s to 6500.0s
20.0s
✩
F8-02
Jog deceleration time
0.0s to 6500.0s
20.0s
✩
F8-03
Acceleration time 2
0.0s to 6500.0s
Model
dependent
✩
F8-04
Deceleration time 2
0.0s to 6500.0s
Model
dependent
✩
F8-05
Acceleration time 3
0.0s to 6500.0s
Model
dependent
✩
F8-06
Deceleration time 3
0.0s to 6500.0s
Model
dependent
✩
F8-07
Acceleration time 4
0.0s to 6500.0s
0.0s
✩
F8-08
Deceleration time 4
0.0s to 6500.0s
0.0s
✩
F8-09
Frequency jump 1
0.00 Hz to max. frequency
0.00 Hz
✩
F8-10
Frequency jump 2
0.00 Hz to max. frequency
0.00 Hz
✩
F8-11
Frequency jump band
0.00 Hz to max. frequency
0.00 Hz
✩
F8-12
Forward/Reverse run switchover
dead-zone time
0.0s to 3000.0s
0.0s
✩
F8-13
Reverse RUN selection
0: Disabled
1: Enabled
0
✩
F8-14
Running mode when frequency
reference lower than frequency
lower limit
0: Run at frequency reference lower limit
1: Stop
2: Run at zero speed
0
✩
F8-15
Droop rate
0.00% to 100.00%
0.00%
✩
F8-16
Accumulative power-on time
threshold
0h to 65000h
0h
✩
F8-17
Accumulative running
time threshold
0h to 65000h
0h
✩
F8-18
Startup protection selection
0: Disabled
1: Enabled
0
✩
F8-19
Frequency detection value 1
0.00 Hz to max. frequency
50.00 Hz
✩
F8-20
Frequency detection hysteresis 1 0.0% to 100.0% (FDT1 level)
5.0%
✩
F8-21
Detection width of target
frequency reached
0.0% to 100.0% (maximum frequency)
0.0%
✩
F8-22
Jump frequency function
0: Disabled
1: Enabled
0
✩
F8-25
Switchover frequency of
acceleration time 1 and
acceleration time 2
0.00 Hz to max. frequency
0.00 Hz
✩