Function
Code
Parameter
Name
Default
Setting
Range
Description
F7-04
LED display
running
parameters
2
0
0000
to
FFFF
If a parameter needs to be displayed during running, set corresponding
bit to 1, and set F7-04 to hexadecimal equivalent.
F7-05
Display stop
parameter
0
0000
to
FFFF
If a parameter needs to be displayed during stop, set corresponding bit
to 1, and set F7-05 to hexadecimal equivalent.
Lowest eight digits
Lowest eight digits
Highest eight digits
Highest eight digits
15 14 13 12
11
10
9
8
Motor speed
Current power-on time (H)
Current running time (Min)
Input pulse frequency (Hz)
Communication reference
Reserved
Main frequency display (Hz)
Auxiliary frequency display (Hz)
15 14 13 12
11
10
9
8
Length value
PLC stage
Load speed
PID reference
Input pulse frequency (Hz)
Reserved
Reserved
Reserved
7
6
5
4
3
2
1
0
PID feedback
PLC stage
Input pulse frequency (kHz)
Running frequency 2 (Hz)
Remaining running time
AI1 voltage before correction (V)
AI2 voltage before correction (V)
AI3 voltage before correction (V)
7
6
5
4
3
2
1
0
Frequency reference (Hz)
Bus voltage (V)
DI state
DO state
AI1 voltage (V)
AI2 voltage (V)
AI3 voltage (V)
Count value
Note: Values with shading are default values.
Note: Once the AC drive is re-powered on after power down, the display includes
the selected parameters before power down by default.