![BENSHAW PowerPro RSI-PPVC-0001-4-3-B-IP20-IM User Manual Download Page 60](http://html1.mh-extra.com/html/benshaw/powerpro-rsi-ppvc-0001-4-3-b-ip20-im/powerpro-rsi-ppvc-0001-4-3-b-ip20-im_user-manual_2735254060.webp)
benshaw.com
60
6
6. PANEL OPERATION
Function
Code
Name
Setting Range
Default
Change
Group F0: Standard Parameters (continued)
F0-07
Final Frequency reference
setting selection
Units position: Frequency reference selection
0: Main frequency reference
1: Main and auxiliary calculation
(based on tens position)
2: Switchover between main and auxiliary
3: Switchover between main and “main
and auxiliary calculation”
4: Switchover between auxiliary and “main
and auxiliary calculation”
Tens position: main and auxiliary
calculation formula
0: Main + auxiliary
1: Main - auxiliary
2: Max. (main, auxiliary)
3: Min. (main, auxiliary)
00
✩
F0-08
Preset frequency
0.00 Hz to max. frequency (F0-10)
50.00 Hz
✩
F0-09
Running direction
0: Forward (FWD/REV indicator off)
1: Reverse (FWD/REV indicator on)
0
✩
F0-10
Max. frequency
50.00 Hz to 500.00 Hz
50.00 Hz
★
F0-11
Setting channel of
frequency upper limit
0: Set by F0-12
1: AI1
2: AI2
3: AI3
4: Pulse reference
5: Communication reference
0
★
F0-12
Frequency reference
upper limit
Frequency lower limit (F0-14) to max. frequency
(F0-10)
50.00 Hz
✩
F0-13
Frequency reference
upper limit offset
0.00 Hz to max. frequency (F0- 10)
0.00 Hz
✩
F0-14
Frequency reference
lower limit
0.00 Hz to frequency upper limit (F0-12)
0.00 Hz
✩
F0-15
Carrier frequency
0.5kHz to 16.0kHz
Model
dependent
✩
F0-16
Carrier frequency adjusted
with load
0: Disabled
1: Enabled
1
✩
F0-17
Acceleration time 1
0.00s to 650.00s (F0-19 = 2)
0.0s to 6500.0s (F0-19 = 1)
0s to 65000s (F0-19 = 0)
Model
dependent
✩
F0-18
Deceleration time 1
0.00s to 650.00s (F0-19 = 2)
0.0s to 6500.0s (F0-19 = 1)
0s to 65000s (F0-19 = 0)
Model
dependent
✩
F0-19
Acceleration/Deceleration
time unit
0: 1s
1: 0.1s
2: 0.01s
1
★
F0-21
Frequency offset of
Auxiliary frequency setting
channel for main and
auxiliary calculation
0.00 Hz to max. frequency (F0-10)
0.00 Hz
✩
F0-22
Frequency reference
resolution
2: 0.01Hz
2
★
F0-23
Retentive of digital setting
frequency upon stop
0: Not retentive 1: Retentive
0
✩
F0-24
Motor parameter group
selection
0: Motor parameter group 1
1: Motor parameter group 2
0
★
F0-25
Acceleration/Deceleration
time base frequency
0: Maximum frequency (F0-10)
1: Frequency reference
2: 100 Hz
0
★
F0-26
Base frequency for UP/
DOWN modification
during running
0: Running frequency
1: Frequency reference
0
★