8 – Fault Conditions
97
Table 22: Fault Conditions
Fault
Code
Fault Displayed
Reaction
Type
Description
Course of Action
71
Follower inverter
fault
*
Occurs on the leader inverter when a
follower inverter faults.
*The Reaction Type is dictated by the
fault declared on the follower inverter.
Examine the fault that occurred on the
follower.
79
Leader shunt
tripped
C,S
Occurs on all follower inverters when
the leader inverter declares a fault with
a shunt trip reaction type.
Examine the fault that occurred on the
leader.
80
FOB fault
C,S
A general FOB (Fiber Optic Board) fault
will always be accompanied by one of
the more specific FOB faults below
(351-354, 451-454, 551-554).
Refer to the specific fault codes below.
81
Cell fault
C,S
A general Cell fault will always be
accompanied by one of the more
specific Cell faults below (301-316, 401-
416, 501-516).
Refer to the specific fault codes below.
82
Follower inverter
PWMs not synced
C,S
Occurs on the leader inverter when a
follower loses PWM Synchronization to
it.
Contact Benshaw
Summary of Contents for M2L 3000
Page 2: ...M2L 3000 Series VFD 2...
Page 6: ...M2L 3000 Series VFD 6...
Page 10: ...M2L 3000 Series VFD 10...
Page 14: ...M2L 3000 Series VFD 14 Part Number Definitions UL Applicable Base Part Numbers...
Page 16: ...M2L 3000 Series VFD 16...
Page 27: ...3 Installation 27 Wiring Schematics Figure 1 MV Drive System Layout...
Page 28: ...M2L 3000 Series VFD 28 Figure 2 Converter Power and Control Circuit Portions...
Page 29: ...3 Installation 29 Figure 3 Inverter Power and Control Circuit Portions...
Page 40: ...M2L 3000 Series VFD 40...
Page 72: ...M2L 3000 Series VFD 72...
Page 124: ...M2L 3000 Series VFD 124...
Page 126: ...M2L 3000 Series VFD 126...
Page 127: ...References 127 References Placeholder for text with left side label...
Page 128: ...M2L 3000 Series VFD 128...
Page 132: ...M2L 3000 Series VFD 132...