M2L 3000 Series VFD
114
Table 22: Fault Conditions
Fault
Code
Fault Displayed
Reaction
Type
Description
Course of Action
600
Interlock fault
C,S
Occurs when digital input 1 on the
Computer Card stops receiving 24
VDC.
Verify that the 24 VDC power supply is
functioning. If not, check the fuse supplying
its input power.
Verify that 24VDC is present across
terminals I/O4 and I/O3 on the breakout
board for the Computer Card IO.
If no devices are installed in the E-stop loop,
verify the yellow jumper wire is installed
between terminals 29 and 31, and that 24
VDC is present on terminal 31.
If there are devices in the E-stop loop, verify
that they are all closed.
604
Inverter Digital Input 4
fault
D
Occurs when
Inverter
Digital Input #4
Function
(IO-03) is set to “External
Fault High”, and 120 VAC is applied to
Digital Input 4 on the Remote IO.
Occurs when
Inverter
Digital Input #4
Function
(IO-03) is set to “External
Fault Low”, and 120 VAC is removed
from Digital Input 4 on the Remote IO.
Verify the control wiring supplied to Inverter
Digital Input 4 on the Remote IO, broken out
to terminal 87 on the terminal block.
View the Inverter I/O Status screen on the
HMI. Verify that the indicator for Inverter DI 4
on the screen toggles as the 120 VAC going
into Inverter Digital Input 4 toggles. If not,
replace the digital input module in the
Remote IO block.
605
Inverter Digital Input 5
fault
D
Occurs when
Inverter
Digital Input #5
Function
(IO-04) is set to “External
Fault High” and 120 VAC is applied to
Digital Input 5 on the Remote IO.
Occurs when
Inverter
Digital Input #5
Function
(IO-04) is set to “External
Fault Low” and 120 VAC is removed
from Digital Input 5 on the Remote IO.
Verify the control wiring supplied to Inverter
Digital Input 5 on the Remote IO, broken out
to terminal 88 on the terminal block.
View the Inverter I/O Status screen on the
HMI. Verify that the indicator for Inverter DI 5
on the screen toggles as the 120 VAC going
into Inverter Digital Input 5 toggles. If not,
replace the digital input module in the
Remote IO block.
606
Inverter Digital Input 6
fault
D
Occurs when
Inverter
Digital Input #6
Function
(IO-05) is set to “External
Fault High” and 120 VAC is applied to
Digital Input 6 on the Remote IO.
Occurs when
Inverter
Digital Input #6
Function
(IO-05) is set to “External
Fault Low” and 120 VAC is removed
from Digital Input 6 on the Remote IO.
Verify the control wiring supplied to Inverter
Digital Input 6 on the Remote IO, broken out
to terminal 89 on the terminal block.
View the Inverter I/O Status screen on the
HMI. Verify that the indicator for Inverter DI 6
on the screen toggles as the 120 VAC going
into Inverter Digital Input 6 toggles. If not,
replace the digital input module in the
Remote IO block.
607
Inverter Digital Input 7
fault
D
Occurs when
Inverter
Digital Input #7
Function
(IO-06) is set to “External
Fault High” and 120 VAC is applied to
Digital Input 7 on the Remote IO.
Occurs when
Inverter
Digital Input #7
Function
(IO-06) is set to “External
Fault Low” and 120 VAC is removed
from Digital Input 7 on the Remote IO.
Verify the control wiring supplied to Inverter
Digital Input 7 on the Remote IO, broken out
to terminal 90 on the terminal block.
View the Inverter I/O Status screen on the
HMI. Verify that the indicator for Inverter DI 7
on the screen toggles as the 120 VAC going
into Inverter Digital Input 7 toggles. If not,
replace the digital input module in the
Remote IO block.
Summary of Contents for M2L 3000
Page 2: ...M2L 3000 Series VFD 2...
Page 6: ...M2L 3000 Series VFD 6...
Page 10: ...M2L 3000 Series VFD 10...
Page 14: ...M2L 3000 Series VFD 14 Part Number Definitions UL Applicable Base Part Numbers...
Page 16: ...M2L 3000 Series VFD 16...
Page 27: ...3 Installation 27 Wiring Schematics Figure 1 MV Drive System Layout...
Page 28: ...M2L 3000 Series VFD 28 Figure 2 Converter Power and Control Circuit Portions...
Page 29: ...3 Installation 29 Figure 3 Inverter Power and Control Circuit Portions...
Page 40: ...M2L 3000 Series VFD 40...
Page 72: ...M2L 3000 Series VFD 72...
Page 124: ...M2L 3000 Series VFD 124...
Page 126: ...M2L 3000 Series VFD 126...
Page 127: ...References 127 References Placeholder for text with left side label...
Page 128: ...M2L 3000 Series VFD 128...
Page 132: ...M2L 3000 Series VFD 132...