3 - Installation
31
Motor Lead Length
The standard drive can operate a motor with a maximum of 600 feet of properly sized cable between the “T” leads
of the drive and those of the motor. For wire runs greater than 600 feet contact Benshaw Inc. for application assis
tance.
Input Line Requirements
The standard drive can operate with a maximum of 300 feet of properly sized cable between the converter and the
inverter.
For wire runs greater than 300 feet, contact Benshaw for application assistance.
DC Lead Length Between Converter and Inverter
The converter and inverter can be located separate from each other. However, the maximum separation distance is
limited by the voltage drop of the wiring. The wire gauge must be chosen to minimize voltage drop. The wiring should com-
ply with all local electrical codes, as stated on previous page. Consult Benshaw for more information.
Torque Requirements for Power Wiring Terminations
Table 16: Slotted Screws and Hex Bolts
Wire size installed in
conductor
Tightening torque, pound-inches (N-m)
Slotted head NO.10 and larger
Hexagonal head-external drive socket wrench
AWG or kcmil
(mm²)
Slot width 0.047
inch (1.2mm) or less
and slot length ¼
inch (6.4mm) or less
Slot width over
0.047 inch (1.2mm)
or slot length ¼
inch (6.4mm) or
greater
Split-bolt connectors
Other connectors
18 - 10
(0.82 - 5.3)
20
(2.3)
35
(4.0)
80
(9.0)
75
(8.5)
8
(8.4)
25
(2.8)
40
(4.5)
80
(9.0)
75
(8.5)
6 - 4
(13.3 - 21.2)
35
(4.0)
45
(5.1)
165
(18.6)
110
(12.4)
3
(26.7)
35
(4.0)
50
(5.6)
275
(31.1)
150
(16.9)
2
(33.6)
40
(4.5)
50
(5.6)
275
(31.1)
150
(16.9)
1
(42.4)
--
--
50
(5.6)
275
(31.1)
150
(16.9)
1/0 - 2/0
(53.5 -64.4)
--
--
50
(5.6)
385
(43.5)
180
(20.3)
3/0 - 4/0
(85.0 - 107.2)
--
--
50
(5.6)
500
(56.5)
250
(28.2)
250 - 350
(127-177)
--
--
50
(5.6)
650
(73.4)
325
(36.7)
400
(203)
--
--
50
(5.6)
825
(93.2)
375
(42.4)
500
(253)
--
--
50
(5.6)
825
(93.2)
375
(42.4)
600 - 750
(304-380)
--
--
50
(5.6)
1000
(113.0)
375
(42.4)
800 - 1000
(406-508)
--
--
50
(5.6)
1100
(124.3)
500
(56.5)
1250 - 2000
(635-1010)
--
--
--
--
1100
(124.3)
600
(67.8)
NOTE: For a value of slot width or length not corresponding to those specified above, the largest torque value associated with the
conductor size shall be marked. Slot width is the nominal design value. Slot length is measured at the bottom of the slot.
Summary of Contents for M2L 3000
Page 2: ...M2L 3000 Series VFD 2...
Page 6: ...M2L 3000 Series VFD 6...
Page 10: ...M2L 3000 Series VFD 10...
Page 14: ...M2L 3000 Series VFD 14 Part Number Definitions UL Applicable Base Part Numbers...
Page 16: ...M2L 3000 Series VFD 16...
Page 27: ...3 Installation 27 Wiring Schematics Figure 1 MV Drive System Layout...
Page 28: ...M2L 3000 Series VFD 28 Figure 2 Converter Power and Control Circuit Portions...
Page 29: ...3 Installation 29 Figure 3 Inverter Power and Control Circuit Portions...
Page 40: ...M2L 3000 Series VFD 40...
Page 72: ...M2L 3000 Series VFD 72...
Page 124: ...M2L 3000 Series VFD 124...
Page 126: ...M2L 3000 Series VFD 126...
Page 127: ...References 127 References Placeholder for text with left side label...
Page 128: ...M2L 3000 Series VFD 128...
Page 132: ...M2L 3000 Series VFD 132...