M2L 3000 Series VFD
118
Table 22: Fault Conditions
Fault
Code
Fault Displayed
Reaction
Type
Description
Course of Action
706
Cell IGBT
Temperature fault
D
Occurs when any cell’s IGBT
temperature reaches 70 °C or 0 °C.
Verify that all fans for the inverter cabinet are
working. Check and replace fuses as
necessary. If one of the fan fuses is blown or
the fan is otherwise inooerable, that fan will
rotate backwards due to the air flow being
forced across the blades.
Verify that the filters for the inverter cabinet
are not clogged. Clean as necessary.
If cooling fans are 3 phase, verify that all 3
fans are rotating counter-clockwise.
707
Cell Board
Temperature fault
D
Occurs when any cell’s control board
temperature reaches 70 °C or 0 °C.
Verify that all fans for the inverter cabinet are
working. Check and replace fuses as
necessary. If one of the fan fuses is blown or
the fan is otherwise inoperable, that fan will
rotate backwards due to the air flow being
forced across the blades.
Verify that the filters for the inverter cabinet
are not clogged. Clean as necessary.
If cooling fans are 3 phase, verify that all 3
fans are rotating in same direction.
714
Input Disconnect Open
C,S
Occurs when one of the digital inputs
Digital Input #4
Function through
Inverter Digital In #8
or
CCI Digital In
#8
is programmed as “Input
Disconnect Feedback” and 120VAC is
removed from that digital input on the
reader I/O.
It is intended for a normally open auxialiary
contact on an input disconnect switch to be
monitored by a digital input programmed as
an “Input Disconnect Feedback” input.
Determine if that auxiliary contact has
opened or malfunctioned.
Verify that 120VAC is being supplied to that
auxiliary contact.
Verify that no other inputs are programmed
as “Input Disconnect Feedback”.
715
Output Disconnect
Open
C,S
Occurs when one of the digital inputs
Digital Input #4
Function through
Inverter Digital In #8
or
CCI Digital In
#8
is programmed as “Output
Disconnect Feedback” and 120VAC is
removed from that digital input on the
reader I/O.
It is intended for a normally open auxialiary
contact on an output disconnect switch to be
monitored by a digital input programmed as
an “Output Disconnect Feedback” input.
Determine if that auxiliary contact has
opened or malfunctioned.
Verify that 120VAC is being supplied to that
auxiliary contact.
Verify that no other inputs are programmed
as “Output Disconnect Feedback”.
Summary of Contents for M2L 3000
Page 2: ...M2L 3000 Series VFD 2...
Page 6: ...M2L 3000 Series VFD 6...
Page 10: ...M2L 3000 Series VFD 10...
Page 14: ...M2L 3000 Series VFD 14 Part Number Definitions UL Applicable Base Part Numbers...
Page 16: ...M2L 3000 Series VFD 16...
Page 27: ...3 Installation 27 Wiring Schematics Figure 1 MV Drive System Layout...
Page 28: ...M2L 3000 Series VFD 28 Figure 2 Converter Power and Control Circuit Portions...
Page 29: ...3 Installation 29 Figure 3 Inverter Power and Control Circuit Portions...
Page 40: ...M2L 3000 Series VFD 40...
Page 72: ...M2L 3000 Series VFD 72...
Page 124: ...M2L 3000 Series VFD 124...
Page 126: ...M2L 3000 Series VFD 126...
Page 127: ...References 127 References Placeholder for text with left side label...
Page 128: ...M2L 3000 Series VFD 128...
Page 132: ...M2L 3000 Series VFD 132...