7 – Parameter Descriptions
85
I/O (Input/Output) Group Parameters
Inverter Digital In Functions (I/O-00 through I/O-15)
I/O-00 (44313)
Inverter
Digital In #1 Function
Values: 0-22
Locked: Converter Warning
I/O-01 (44314)
Inverter
Digital In #2 Function
Locked: Converter Fault
I/O-02 (44315)
Inverter
Digital In #3 Function
Locked: Main Cont Fdbk
I/O-03 (44316)
Inverter
Digital In #4 Function
Default: NONE
I/O-04 (44317)
Inverter
Digital In #5 Function
Default: Run FWD
I/O-05 (44318)
Inverter
Digital In #6 Function
Default: Run REV
I/O-06 (44319)
Inverter
Digital In #7 Function
Default: Stop
I/O-07 (44320)
Inverter
Digital In #8 Function
Default: NONE
I/O-08 (44321)
Inverter
Digital In #9 Function
Default: NONE
I/O-09 (44322)
Inverter
Digital In #10 Function
Default: NONE
I/O-10 (44323)
Inverter
Digital In #11 Function
Default: NONE
I/O-11 (44324)
Inverter
Digital In #12 Function
Default: NONE
I/O-12 (44325)
Inverter
Digital In #13 Function
Default: NONE
I/O-13 (44326)
Inverter
Digital In #14 Function
Default: NONE
I/O-14 (44327)
Inverter
Digital In #15 Function
Default: NONE
I/O-15 (44328)
Inverter
Digital In #16 Function
Default: NONE
Digital Input Options
For use with external control logic, the following options are available as input selections
for I/O-00 through I/O-15:
0:
Run Forward / Run Reverse -
Allows start and stop capabilities from any external con-
trol logic (such as start and stop pushbuttons, or PLC control). To enable, the Control
Source (Local or Remote, I/O-136 or I/O-137) must be set to “Digital Input”.
1:
Stop
- Enables use of 3-wire start logic (for use with external Start and Stop buttons).
2:
Fault Reset
- Enables reset of fault conditions from external control logic (pushbutton
or PLC).
3:
Run Enable / Run Disable
- For use with external control logic, all Run Enable inputs
must be on, and all Run Disable inputs must be off, for the drive to run. If the motor is
running and a Run Enable is removed, the motor will stop according to the setting of the
Stop Mode (FUNCTION-01).
4:
Local/Remote
- Selects whether the Local Control Source and Speed Reference
Source or the Remote Control Source and Speed Reference Source are the control and
speed reference sources.
5: When the signal is low, start/stop and speed reference functions are controlled by the
Local Control Source and the Local Speed Reference Source
6: When the signal is high, start/stop and speed reference functions are controlled by the
Remote Control Source and the Remote Speed Reference Source.
7:
DC Brake Enable / DC Brake Disable
- For use with external control logic, all DC
Brake Enable inputs must be on, and all DC Brake Disable inputs must be off, for the DC
Brake feature to function when stopping. If not enabled, the drive will allow the motor to
coast instead of employing the DC Brake.
8:
External Fault High / External Fault Low
- Allows external sources to trigger an exter-
nal fault to the assigned digital input by either applying or removing voltage (high or low).
The drive will produce a unique code indicating the digital input source of the fault.
Summary of Contents for M2L 3000
Page 2: ...M2L 3000 Series VFD 2...
Page 6: ...M2L 3000 Series VFD 6...
Page 10: ...M2L 3000 Series VFD 10...
Page 14: ...M2L 3000 Series VFD 14 Part Number Definitions UL Applicable Base Part Numbers...
Page 16: ...M2L 3000 Series VFD 16...
Page 27: ...3 Installation 27 Wiring Schematics Figure 1 MV Drive System Layout...
Page 28: ...M2L 3000 Series VFD 28 Figure 2 Converter Power and Control Circuit Portions...
Page 29: ...3 Installation 29 Figure 3 Inverter Power and Control Circuit Portions...
Page 40: ...M2L 3000 Series VFD 40...
Page 72: ...M2L 3000 Series VFD 72...
Page 124: ...M2L 3000 Series VFD 124...
Page 126: ...M2L 3000 Series VFD 126...
Page 127: ...References 127 References Placeholder for text with left side label...
Page 128: ...M2L 3000 Series VFD 128...
Page 132: ...M2L 3000 Series VFD 132...