7 – Parameter Descriptions
83
AFN (Advanced Function) Group Parameters
AFN-00 (40139)
Skip Frequency Enable
Value: 0: Disabled
1: Enabled
Default: 0
AFN-01 (40140)
Skip Frequency Low 1
Value: 0.00 – 300.00 Hz
Default: 20.00
AFN-02 (40141)
Skip Frequency High 1
Value: 0.00 – 300.00 Hz
Default: 21.00
AFN-03 (40142)
Skip Frequency Low 2
Value: 0.00 – 300.00 Hz
Default: 30.00
AFN-04 (40143)
Skip Frequency High 2
Value: 0.00 – 300.00 Hz
Default: 31.00
AFN-05 (40144)
Skip Frequency Low 3
Value: 0.00 – 300.00 Hz
Default: 40.00
AFN-06 (40145)
Skip Frequency High 3
Value: 0.00 – 300.00 Hz
Default: 41.00
The Skip Frequency function locks out certain frequencies that can cause resonance in
the driven equipment. The drive will accelerate and decelerate through these frequen-
cies but will not remain at the locked out frequencies. Three different Skip Frequency
ranges can be programmed (AFN-01 through AFN-06).
AFN-07 (40146)
Dwell Enable
Value: 0: Disabled
1: Enabled
Default: 0
The Dwell Function enables the drive to ramp to the programmed
Dwell Frequency
(AFN-08), and remain there for the programmed
Dwell Time
(AFN-09) before continu-
ing the programmed acceleration or deceleration ramp.
AFN-08 (40147)
Dwell Frequency
Value: 0.00 – 300.00 Hz
Default: 0.00
When the Dwell function is enabled in AFN-07, this value determines the frequency at
which the drive will remain for the duration programmed in
Dwell Time
(AFN-09).
AFN-09 (40148)
Dwell Time
Value: 0.01 – 600.00 Seconds Default: 0.01
When the Dwell function is enabled in AFN-07, this value determines the duration of
time that the drive will remain at the frequency programmed in
Dwell Frequency
(AFN-
08).
AFN-10 (40164)
Flying Start Current Level
Value: 1 – 99 %
Default: 25
When the Start Mode (FUNCTION-00) is set to “Flying Start”, a sequence is enabled to
“catch the motor on the fly”. This sequence can be defined in the following steps:
1 -
Current Application
: The drive applies a low level current to the motor
2 -
Frequency Ramp
: Beginning at the selected starting (AFN-14) fre-
quency, the drive ramps output frequency down until the speed of the motor
is matched
3 -
Voltage Adjust
: The drive sets the voltage to the appropriate level based
on the frequency determined in Step 2.
Once this sequence is complete, the drive then accelerates along the programmed ac-
celeration profile.
Flying Start Current Level defines the low level current output used to begin the Flying
Start sequence Step 1. While in Flying Start sequence Step 2, the output voltage is re-
duced as necessary to maintain current below the Flying Start Current Level.
AFN-11 (40165)
Flying Start Current
Application Time
Value: 0.01 – 10.00 Seconds
Default: 5.00
Flying Start Current Application Time
defines the length of time for Step 1 of the Flying
Start sequence. The drive applies the Flying Start Current Level (AFN-10) before con-
tinuing with the flying start sequence.
Summary of Contents for M2L 3000
Page 2: ...M2L 3000 Series VFD 2...
Page 6: ...M2L 3000 Series VFD 6...
Page 10: ...M2L 3000 Series VFD 10...
Page 14: ...M2L 3000 Series VFD 14 Part Number Definitions UL Applicable Base Part Numbers...
Page 16: ...M2L 3000 Series VFD 16...
Page 27: ...3 Installation 27 Wiring Schematics Figure 1 MV Drive System Layout...
Page 28: ...M2L 3000 Series VFD 28 Figure 2 Converter Power and Control Circuit Portions...
Page 29: ...3 Installation 29 Figure 3 Inverter Power and Control Circuit Portions...
Page 40: ...M2L 3000 Series VFD 40...
Page 72: ...M2L 3000 Series VFD 72...
Page 124: ...M2L 3000 Series VFD 124...
Page 126: ...M2L 3000 Series VFD 126...
Page 127: ...References 127 References Placeholder for text with left side label...
Page 128: ...M2L 3000 Series VFD 128...
Page 132: ...M2L 3000 Series VFD 132...