Reactive Factor Controller CX plus
53
700 Settings MODBUS (communication interface)
Contains settings in order to parametrise the MODBUS-RTU communication interface (RS485).
NOTE:
This submenu is only available with the option -MB.
700
Settings MODBUS
MENU
FUNCTION
AREA
701
Baud rate
1200,2400,4800,
9600,19200,
38400,57600,
115200
Setting of the baud rate (transmission rate) of the communication interface.
702
Parity and stop bit
EVEN/ODD/
NONE
Setting of the parity and the stop bits of the communication interface.
EVEN:
Parity =
Even
Stop bits =
1
ODD:
Parity =
Odd
Stop bits =
1
NONE:
Parity =
None
Stop bits =
2
703
MODBUS slave address
1…247
Setting of the MODBUS slave address (BUS address)
NOTE:
The BUS address may only be assigned once within the BUS.
9.12 Alarm memory menu
The last 10 occurred and signalled alarms are saved and displayed in the alarm memory. The latest
alarm is on memory space 1, the oldest alarm on memory space 10. The alarm memory works as
sliding buffer. If a new alarm is signalled, this is saved at the first space. In the process, all previously
available entries (1-10) from memory space 1 onwards are each moved on by one memory space. As
a consequence, the alarm previously saved under memory space 10 is deleted. The alarm memory is
non-volatile. This may be deleted completely by simultaneously pressing the keys "
" and "
" for
approx. 3 s in the alarm memory menu. The alarm memory may also be deleted under SETUP/606.
NOTE:
As a consequence, all alarms signalled on the display and the alarm relay are also reset, if no
alarm is active anymore.