Technical documentation
Rev. 02
Reactive Factor Controller CX plus
17
The second temperature limit has been exceeded.
Steps will be or were already switched off one by
one.
Set limit value of the operating hours has been
exceeded.
/
Set limit of the maximum permissible switching
cycles of one or several steps has been exceeded.
Error code and step number are flashing
alternatingly.
Only the smallest affected step number is displayed.
/
Set limit of the maximum permissible operating
hours of one or several steps has been exceeded.
Error code and step number are flashing
alternatingly.
Only the smallest affected step number is displayed.
If several alarms are active, the alarm messages are exchanged cyclically.
Example: U and I-Low alarm are active, the alarm messages are displayed as follows: 3 times error
code “
U
”, then 3 times “
I
”, then again 3 times starting with “
U
” etc.
In addition to the alarm messages, the following error and status messages are displayed.
Error messages:
/
The automatic initialisation (AI) was cancelled due to
an error. The control was switched off.
An active error message can be reset by pressing the
(ESC) key for 3 s.